beautypg.com

Retrotec RSH Pressure Relief Vents User Manual

Page 5

background image

QG700

Page 5 of 8

rev-2010-08-13

h) Where the wall liner meets the back of the PRV, seal gap with a bead of intumescent fire-rated

caulk.

i) Check that each and every blade of the PRV opens freely. If blades are rubbing against the side

casing check to make sure the frame of the PRV has been fitted square and is not twisted and
there is no part of the wall opening that is jamming on the vent casing. (it may be possible to
free slightly rubbing blades by tapping out casing where they touch, with a hammer).