LuMIN8 Installation Instructions
5
Dipswitch Settings
Note:
All switches must be positioned before powering up.
SW
Description
SW1:
SCB/SAB
Used to select SAB or SCB mode for the sounder.
ON (SCB): Current for the sounder will be drawn from the sounder’s rechargeable
battery.
OFF (SAB): Current for the sounder will be drawn from the control panel.
SW2-SW4:
A1, A2, A3
The operation of the dipswitches varies according to the sounder operation mode (BUS or
Stand Alone) as defined by SW5.
Stand Alone Mode (SW5 OFF):
SW2 (A1) Used to control the Sounder Current.
ON: Low current mode. The sound output will be reduced to 105dB 150mA
(1 piezo).
OFF: Normal current mode. The sound output will be 111dB 350mA (1 piezo).
SW3 (A2): Used to select the Sounder Sound.
ON:
=Low Sweep tone
OFF: High Sweep tone
SW4 (A3): Used to define Engineer Maintenance Mode (2 options available).
ON: The Engineer may disable the box tamper (built-in bell tamper ring) by removing
the 12V+ for 3 seconds. This mode will be indicated by a single flashing LED. To
return the sounder to the normal mode, remove the power for 10 seconds.
OFF: Application of 12V to the SET+ input will place the sounder in Engineer
Maintenance Mode. When in Engineer Mode, the sounder tamper signal is
active.
BUS (Serial) Mode (SW5 ON):
SW2-SW4:
=Used to set a unique ID number for the sounder when connected in serial
mode (ProSYS or GT serial control panels).
============================================
=
SW5:
BUS/STD
Defines the operation mode of the sounder.
ON (BUS): BUS (Serial) mode. Use when connecting to ProSYS Freecom or GT
control panels.
OFF (STD): Stand Alone mode.