Appendix 2: Recommended Cable Distances Using 7/0.2 Alarm Cable
in Serial Mode
Standard 7/0.2 alarm cable gives some limitation to the distance that a sounder may be wired away
from the control panel for reliable operation. To overcome this limitation increase the number of cores
used for the 0V and 12V feed to the sounder.
Control
Panel
Max Distance = 35m(Single Piezo)
25m(Twin Piezo)
4 Core Cable
LuMIN8 1
SCB
4 Core Cable
LuMIN8 2
SCB
Control
Panel
Max Distance = 71m(Single Piezo)
50m(Twin Piezo)
LuMIN8 1
SAB
6 Core Cable
Control
Panel
Max Distance = 300m
LuMIN8 2
SCB
6 Core Cable
Control
Panel
Max Distance = 71m(Single Piezo)
50m(Twin Piezo)
LuMIN8 1
SAB
6 Core Cable
LuMIN8 2
SCB
6 Core Cable
Control
Panel
Max Distance = 60m
LuMIN8 1
SAB
6 Core Cable
LuMIN8 2
SCB
6 Core Cable
PSU
LuMIN8 1
SAB
Control
Panel
Control
Panel
Max Distance = 100m
LuMIN8 1
SCB
6 Core Cable
LuMIN8 2
SAB
6 Core Cable
PSU
ZEX
Max Overall Distance = 100m
Max Overall Distance = 140m
Note:
When the sounder is
connected to the control
panel in Serial mode only 4
cores are required.
When 6 Core Cable is
used, 2 cores should be
used for 0V connection
and 2 cores for the +12V
connection.
Max Overall Distance = 50m