Assessment of Functional Safety

The BG Call Point is intended for use in a safety system conforming to the requirements of IEC61508.

Sira Test & certification Ltd has conducted a Failure Modes Effect and Diagnostic Analysis (FMEDA) of

the BG Break Glass unit against the requirements of IEC61508-2 using a proof test interval of 8760hrs.

The Call Point is classed as a Type A device.

BG BREAKGLASS UNIT

Safety Function of BG Break Glass Unit:

‘To raise the alarm upon breaking the glass’

Architectural constraints:

Type A

HFT=0

SFF= 97%

Proof Test Interval

=8760Hrs

MTTR = 8 Hrs

SIL3

Random hardware failures:

DD

= 0

DU

= 5.72E-07

SD

= 0

SU

= 2.04E-05

Probability of failure on demand:

PFD

AVG

=2.51E-03

(Low Demand Mode)

SIL2

Probability of Dangerous failure on

safety function:

PFH = 5.72E-07

(High Demand Mode)

SIL2

Hardware safety integrity compliance

[1]

Route 1

H

Systematic safety integrity compliance

Route 1

S

Systematic Capability

SC2

Overall SIL-capability achieved

SIL 2 (Low Demand)

SIL 2 (High Demand)