This mode allows a proper mix of the air in the room of installation
and better cooling of the structure of the fireplace stove.
(Figure 6)
ALWAYS CONNECT THE TWO DUCTS AND RUN THEM
OUTSIDE. IF YOU DO NOT COMPLY WITH THIS RULE,
THE FAN MAY DRAW IN THE AIR INTENDED FOR
COMBUSTION
Remember that:
All of the air intakes must be equipped with shutters than can
be controlled from the outside and that are equipped with
insect protection.
The air intake section is considered net, therefore the area of
any obstructions must be considered (mesh, etc.)
The filters or meshes need to be cleaned periodically to ensure
air can pass through them.
Do not for any reason obstruct the air intakes if the
fireplace stove or ventilation kit is in operation
4.4. POSITIONING
The VIVO fireplace stove can be placed in a corner or along a wall.
It can be installed at the desired height, providing a suitable support
during work.
Always evaluate the structural condition of the surface which
will take the weight, and always leave a minimum 5 cm
airspace between the stove and any walls.
Install dry the fire bed of the cladding leaving an opening of 1 cm
for the insulation.
For installation near flammable material, comply with the
following minimum safe distances:
(Figure 7)
A = 100 mm (distance from the sides and back)
B = 80 mm (insulating material)
C = 200 mm (height above floor)
If the stove is positioned over a floor or close to
walls made of flammable materials, it is advisable to
use sufficient insulation.
Figure 6 – Air intakes for ducts of fan and
combustion air intake.
A
A
A
B
B
C
Figura 7 – Installation near flammable
material
B
A