Technical characteristics, Rotary disconnect switches – Eaton Electrical Disconnect Switches User Manual
Page 17
16
For more information visit us at: www.eatonelectrical.ca
December 2004
Technical Characteristics
Table 14. CSA Technical Characteristics
Table 15. CSA/UL Technical Characteristics C, V, S & F Frame Non-Fused and Fusible
ᕃ
2-pole in series.
ᕄ
3-pole in series.
ᕅ
15 x 15 shaft for non-fusible and 10 x 10 shaft for fusible, 400A
ᕆ
DC rating on non-fusible 600A only, no DC rating for 600A fusible.
ᕇ
Values on left = non-fusible. Values on right = fusible.
Description
R-Frame
W-Frame
Catalogue Number
Catalogue Number
C362NR30MD /C362TR30MD C362NR40MD /C362TR40MD C362NW60MD /C362TW60MD
C362NW80MD /C362TW80MD
Rating Ampere
30A
40A
60A
80A
CSA C22.2#14/CEC Rule 28-602/ (3)(b)
CSA
CSA
CSA
CSA
Short Circuit Rating kA with Fuses
10
10
10
10
Fuse Class
J
J
J
J
Fuse Rating (A)
60
60
100
100
Maximum CSA
120V AC
2
3
5
7.5
Horsepower
208V AC
5
7.5
10
15
Ratings (3-Phase)
220 – 240V AC
7.5
10
15
20
440 – 480V AC
15
20
30
40
600V AC
20
25
40
50
Maximum CSA
Horsepower
Ratings (1-Phase)
120V AC
1.5
2
2
3
208V AC
2
3
5
7.5
240V AC
3
3
7.5
10
480V AC
7.5
7.5
15
20
600V AC
10
10
20
30
Electrical Endurance
(Operation Cycles)
6000
6000
6000
6000
Mechanical Endurance (Operation Cycles)
6000
6000
6000
6000
Terminal Lugs
Wire Size
#14 – #4
#14 – #4
#14 – #1
#14 – #1
Wire Type
Cu
Cu
Cu
Cu
Weight in Lbs. (kg)
.44 (.20)
.44 (.20)
.66 (.30)
.66 (.30)
Catalogue Number
C Frame
V Frame
V Frame
V Frame
V Frame
S/V Frame
S/F Frame
S/F Frame
S Frame
S Frame
C362UC30
C362UC30CT
C363UC30JT
C363UV30C
C363UV30J
C363UV30CT
C363UV30JT
C362UV60
C363UV60J
C363UV60JT
C362UV100
C363UV100J
C363UV100JT
C362UV200
C363UV200J
C363UV200JT
C362US400
C363UV400J
C363UV400JT
C362US600
C363UF600J
C362US800
C363UF800L
C362US1000 C362US1200
Rating Ampere
30
30
60
100
200
400
600
800
1000
1200
CSA C22.2 #4/UL98
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
CSA/UL
Short Circuit Rating kA
with Fuses
50
CC-100
J-200
200
200
200
200
200
100/200
➄
100
100
Fuse Class
CC / J
CC / J
J
J
J
J
J
L
L
L
Fuse Rating (A)
30
30
60
100
200
400
600
800
1000
1200
Maximum UL
Horsepower
(3-Phase)
240V AC 7.5
7.5
15
30
60
125
200
250
250
250
480V AC 15
15
30
60
125
250
400
500
500
500
600V AC 20
20
50
75
150
350
350
500
500
500
DC 125V 3
ᕃ
3
ᕃ
3
ᕃ
7.5
ᕃ
15
ᕃ
20
ᕃ
20
ᕃ
➃
—
—
—
DC 250V 5
ᕃ
5
ᕃ
10
ᕄ
20
ᕄ
40
ᕄ
50
ᕄ
50
ᕄ
➃
—
—
—
Electrical
Endurance
(Opera-
tion
Cycles)
6000
6000
6000
6000
6000
1000
1000
500/1000
➄ 500
500
Mechanical
Endurance
(Opera-
tion
Cycles)
10,000
10,000
10,000
10,000
8000
6000
6000/
5000
➄
3500/
5000
➄
3500
3500
Shaft Size
Square
Inches
(mm)
.2 x .2
(5 x 5)
.4 x .4
(10 x 10)
.4 x .4
(10 x 10)
.4 x .4
(10 x 10)
.4 x .4
(10 x 10)
.59 x .59
(15 x 15)/
.4 x .4
(10 x 10)
ᕅ
.59 x .59
(15 x 15)
.59 x .59
(15 x 15)
.59 x .59
(15 x 15)
.59 x .59
(15 x 15)
Switch Operat-
ing Torque
lb. in.
21
88
88
88
106
320/132
320
320
320
320
Terminal Lugs
Wire Size Min-
Max
Non-
Fused
#14 – #10
#14 – #10
#10 – #3
#10 – #3
#6-– 3/0
(2)#2-(2)
600mcm
(2)#2-(2)
600mcm
(3)#2-(3)
600mcm
(3)#2-(3)
600mcm
(4)#2-(4)
600mcm
Fusible
#14 – #10
#14 – #10
#10 – #3
#14 – 2/0
#6-– 3/0
(2)#2-(2)
600 mcm
(2)#2-(2)
600mcm
(3)#2-(3)
600 mcm
–
–
Weight in Lbs. (kg)
1.1 (.50)
1.1 (.50)
2.0 (.91)
2.5 (1.1)
4.4 (2.0)
8.8 (4.0)
9.9 (4.5)
22.0 (10.0)
28.6 (13.0)
30.8 (14.0)
Rotary Disconnect Switches