Initial installation, Preparation for installation, Clearances to combustibles – Enviro ASCOT VENTED GAS FIREPLACE HEATER User Manual
Page 12
Initial Installation
QUALIFIED INSTALLERS ONLY
WARNING:
Operation of this heater when not connected to a properly installed and maintained venting system can
result in carbon monoxide (CO) poisoning and possible death.
P
REPARATION
F
OR
I
NSTALLATION
:
• Remove the packaging from the appliance, and check to make sure there is no damage. If damage is
found, please report it to both the carrier and your dealer as soon as possible.
• Before beginning, carefully check the glass door and the log set
• Locate a position where the flue system of the stove can be properly installed without damaging the
integrity of the building; e.g. cutting a wall or ceiling joist.
• Check stove and flue system clearance requirements.
• Locate the stove where it can be accessed by a gas supply line.
• Locate the stove in a large and open room that is centrally located in the house. This will optimize heat
circulation and comfort.
• As the stove can be equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8
m) of the stove.
• The flow of combustion and ventilation air must not be obstructed.
C
LEARANCES
TO
C
OMBUSTIBLES
:
A) Sidewall to unit
10 inches (254 mm)
B) Backwall to unit
21⁄2 inches (64 mm)
C) Corner to unit
21⁄2 inches (64 mm)
D) Ceiling bottom of unit 60 inches (1524 mm)
E) Floor
0 inches
(0 mm)
Note: Must have hearth pad if installed on a
carpeted surface.
If this unit is installed in an alcove the alcove must meet
these minimum dimensions:
Width
48 inches (1219 mm)
Height
60 inches (1524 mm)
Maximum Depth
24 inches (610 mm)
CLEARANCES MUST BE SUFFICIENT TO ALLOW ACCESS FOR MAINTENANCE AND SERVICE.
�
�
�����
���� ����
��
�
�
�
��
�
�
�
��
��
�
�������� ����
�
�
��
��
�
�
�
��
�
Figure 12: Clearances to combustibles.