Minimum Wall and Ceiling Clearances (Figure 4)
Sidewall Clearances: The clearance from the inside of the fireplace

to any combustible wall should not be less than 2".
Fireplace Side and Back Clearances: The fireplace outer casing

sides and back have zero clearance to combustibles.
Ceiling Clearances: The ceiling height should not be less than 36"

from the top of the hood.
Mantel Clearances: Vent free fireplace models must use the hood

supplied with the fireplace. If a combustible mantel is installed,

it must meet the clearance requirements detailed above.

Figure 4

2”

36”

COMBUSTIBLES

ALLOWED

MANTEL

HOOD

2”

7”

4”

9 3/4”

4 1/4”

6”

12 ½”

8”

15 1/4”

18”

10”

12”

Figure 5

Mantel Clearances (Figure 5)

Checking Manifold Pressure

VFP(32,36)FP(30,31)LN (Natural gas) will have a manifold

pressure of approximately 3.5" w.c. (.871kPa) for maximum input or

1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet

with the inlet pressure to the pressure regulator from a minimum

of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a

maximum of 10.5" w.c. (2.614kPa). VFP(32,36)FP(20,21)LN

(Natural gas) will have a manifold pressure of approximately 6.0"

w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure

to the pressure regulator from a minimum of 7.0" w.c. (1.74kPa)

for the purpose of input adjustment to a maximum of 10.5" w.c.

(2.615kPa). VFP(32,36)FP(30,31)LP (Propane gas) will have a

manifold pressure approximately 10.0"w.c. (2.49kPa) for maximum

input or 4.9"w.c. (1.220kPa) for minimum input at the pressure

regulator outlet with the inlet pressure to the pressure regulator

from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input

adjustment to a maximum of 13.0"w.c. (3.237kPa).

VFP(32,36)FP(20,21)LP (Propane gas) will have a manifold

pressure approximately 10.0"w.c. (2.49kPa) at the pressure

regulator outlet with the inlet pressure to the pressure regulator

from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input

adjustment to a maximum of 13.0"w.c. (3.237kPa).
A test gage connection is located downstream of the gas appliance

pressure regulator for measuring gas pressure. The connection is

a 1/8 inch (3mm) N.P.T. plugged tapping.
VFP(32,36)FP(30,31) Millivolt Control

The valve regulator controls the burner pressure which should be

checked at the pressure test point. Turn captured screw counter

clockwise 2 or 3 turns and then place tubing to pressure gauge

over test point (Use test point “A” closest to control knob). After

taking pressure reading, be sure and turn captured screw clockwise

firmly to re-seal. Do not over torque. Check for gas leaks.

GAS SUPPLY (continued)

CLEARANCES