beautypg.com

Model 1600 ins fireplace insert – Enviro ENVIROFIRE 1600 User Manual

Page 12

background image

MODEL 1600 INS FIREPLACE INSERT

Unless you are experienced, we recommend
installation by your dealer or a professional installer.

Install only in a masonry fireplace at least 25” (635
mm) wide, 22” (560 mm) high and 14” (356 mm)
deep with an approved lined chimney at least 15 ft
(4.6 m) high, both of which have been constructed
in accordance with the building code. Be sure the
fireplace and chimney are clean and sound without
any cracks or loose mortar. Do not remove any
bricks or mortar from the fireplace.

1.

Remove any fireplace damper or fasten in a

permanent open position.

(IN CANADA)

2.

The stove is vented with a 6” stainless steel liner

that goes directly to the top of the chimney and is
covered with a rain cap. The chimney top is sealed
with a flashing or steel plate that supports the
weight of the chimney liner. The installation must
conform to the liners manufacturer’s instructions.

This fireplace must be installed with a continuous
liner of 6” diameter (CANADA ONLY) extending
from the fireplace insert to the top of the chimney.
The chimney liner must conform to the class 3
requirements of CAN/ULC-S635, standard for lining
systems for existing masonry or factory built
chimneys and vents, or CAN/ULC-S640, Standards
for lining systems for new masonry chimneys.


(IN U.S.A.)
The appliance when installed, must follow local building codes, in the absence of local building codes, with the
current NFPA 211 Standard for Chimneys, fireplaces, vents, and Solid Fuel Burning Appliances

Screw or Nail the metal plate provided form the manufacture to the inside of the fireplace.
METAL TAG: “THIS FIREPLACE HAS BEEN ALTERED TO ACCOMMODATE A FIREPLACE INSERT AND
SHOULD BE INSPECTED BY A QUALIFIED PERSON PRIOR TO THE RE-USE AS A CONVENTIONAL
FIREPLACE.”

REQUIRED CLEARANCES TO COMBUSTIBLES FROM INSERT:

Minimum clearances to a unshielded side wall:
17” (430 mm)
Minimum clearances to a unshielded mantle:
28” (710 mm)
Minimum top facing clearance:

28” (710 mm)
Minimum side facing clearance:

1” ( 25 mm)

If there is a combustible floor in front of the masonry
fireplace, the fireplace insert must be 8” (205 mm) above
the combustible floor, and floor protection must be provided
18” (455 mm) in front of the fireplace insert and 8 “(205
mm) to each side of the unit.

12

This manual is related to the following products: