Troubleshooting, 2 output voltage pid, Table 8 fault – Yaskawa PID A1000 User Manual
Page 9

2 Output Voltage PID
YASKAWA TM.A1000SW.061 Output Voltage PID A1000 Custom Software Supplement
9
Table 6 Multi-Function Input Settings (H1- )
Table 7 Multi-Function Output Settings (H3- )
Troubleshooting
Table 8 Fault
U7-03
0662h
Voltage Error
Voltage Error
Difference between the voltage setpoint (P1-02) and the voltage
feedback.
10V:100 Vac
0.1 Vac
– – – – – – Y
U7-04
0663h
Output Voltage PID Output
Voltage PID Out
Displays the contribution of the output voltage regulator.
10V:100 Vac
0.1 Vac
– – – – – – Y
U7-05
0664h
Output Current Voltage
Compensation Level
Iac Comp Voltage
Displays the contribution of the output current V compensation.
10V:100 Vac
0.1 Vac
– – – – – – Y
U7-06
0665h
Iq Voltage Compensation
Level
Iq Comp Voltage
Displays the contribution of the Iq Voltage compensation.
10V:100 Vac
0.1 Vac
– – – – – – Y
Setting
Description
19
PID Disable
Closed: Output Voltage PID is disabled.
30
PID Integral Reset
Closed: Output Voltage PID Integrator is reset to zero.
31
PID Integral Hold
Closed: Output Voltage PID Integrator is held at its present value.
Setting
Description
Analog input scaling
Control Method/
Access Level
20
Output Voltage Feedback
Output V Fdbk
Full scale: 10V = P1-07 Value
– – – – – – Y
21
Output Voltage Setpoint
V Setpoint
Full scale: 10V = P1-07 Value
– – – – – – Y
Fault Display
Description
Cause
Countermeasures
oPE12
Energy Save ON
The energy savings feature was enabled when the
output voltage PID was enabled.
Parameter b8-01 was set to "Enable" when
parameter P1-08 is set to "Enable" and control
method is V/f.
Set b8-01 = 0 or Set P1-08 = 0
Monitor No.
MEMOBUS/
Modbus
Address
Monitor Name
Digital Operator Display
Description
Analog output
scaling
Unit
Control Method/
Access Level