2 Output Voltage PID

8

YASKAWA TM.A1000SW.061 Output Voltage PID A1000 Custom Software Supplement

Table 4 Additional Function Text

Table 5 Monitors

P1-04

0603h

Output Voltage PID Integral Limit
Output V I Lmt

Limit for the integral function.
100% = E1-05

0.00 to 100.0

100 %

Yes

– – – – – – Y

P1-05

0604h

Output Voltage PID Derivative
Time
Output V Deriv T

Sets the amount of derivative action for the output
voltage regulator.

0.00 to 10.00

0.00 sec

Yes

– – – – – – Y

P1-06

0605h

Output Voltage PID Limit
Output V Limit

Limit for the entire output voltage regulator
function (P + I + D).
100% = E1-05

0.0 to 100.0

100 %

Yes

– – – – – – Y

P1-07

0606h

Analog Full Scale Voltage
Ana Full Scale V

Sets the scaling for the output voltage regulator
feedback input (H3-…… = 20) and the Analog
Output Voltage Setpoint (H3-…… = 21).

0.0 to 1000

600 Vac

No

– – – – – – Y

P1-08

0607h

Output Voltage PID Select
Output V Select

Selects whether the output voltage control is active
or not.
0: Disabled
1: Enabled

0 to 1

1

No

– – – – – – Y

P2-01

060Ah

Output Current Voltage
Compensation
Iac RMS Comp V

Adds output voltage based upon output current.

0 to 200.0

0.0 Vac

Yes

– – – – – – Y

P2-02

060Bh

Output Current Voltage
Compensation Filter Time
Iac RMS FiltTime

1st order filter on the RMS output current.

0.01 to 1.00

0.01 sec

Yes

– – – – – – Y

P2-03

060Ch

Iq Voltage Compensation
Iq Comp V

Adds output voltage based upon Iq (Torque
Producing Current).

0.0 to 200.0

0.0 Vac

Yes

– – – – – – Y

P2-04

060Dh

Iq Voltage Compensation Filter
Time
Iq Filt Time

1st order filter on the Iq output current.

0.01 to 1.00

0.01 sec

Yes

– – – – – – Y

Function No.

Function Name

Digital Operator Display

P

Output Voltage Control

Output V Control

P1

Output Voltage PID

Output V PID

P2

Voltage Compensation

Voltage Comp

U7

Output Voltage Control

Output V Control

Monitor No.

MEMOBUS/

Modbus

Address

Monitor Name

Digital Operator Display

Description

Analog output

scaling

Unit

Control Method/

Access Level

U7-02

0661h

Voltage Feedback
Voltage Feedback

Displays the analog feedback sensor voltage, scaled to P1-08.

N/A

0.1 Vac

– – – – – – Y

No.

MEMOBUS/

Modbus

Address

Name

Digital Operator Display

Description

Range

Default

Value

Change

During

Run

Control Method/

Access Level