2 Output Voltage PID

YASKAWA TM.A1000SW.061 Output Voltage PID A1000 Custom Software Supplement

7

‹

Related Parameters and Functions

The legend below is used in this section to indicate which parameters are available in which control modes.

The parameter tables in this section are used to set up the drive for operation with the software.

Table 2 Modified Parameters

Table 3 Additional Parameters

No.

MEMOBUS/

Modbus

Address

Name

Digital Operator Display

Description

Range

Default

Value

Change

During

Run

Control Method/

Access Level

A1-02

0102h

Control Method
Control Method

Sets the control method.
0: V/Hz
1: V/Hz w/PG
2: Open Loop Vector
3: Flux Vector
4: PM VVC1
5: PM OLV
6: PM CLV

0 to 6

0

No

YYYYYYY

H3-06

0414h

Terminal A3 Function Selection
Terminal A3 Sel

Selects the function of the Terminal A3 Multi-
Function Analog Input.
0: Freq Ref Bias
1: Freq Ref Gain
. . .
20: Output V Fdbk
21: V Setpoint

0 to 21

20

No

YYYYYYY

n9-10

05D9h

Automatic Voltage Regulator Time
AVR Time

The AVR modifies output voltage based on bus
voltage.

0.0 to 100.0

5.0 ms

No

– – – – – – Y

n9-14

05DDh

Power Factor Angle Filter 1
Pwr Angle Flt 1

Sets the response of the power factor angle filter.

0 to 1000

10 ms

No

– – – – – – Y

n9-15

05DEh

Power Factor Angle Filter 2
Pwr Angle Flt 2

Sets the response of the power factor angle filter.

0 to 1000

10 ms

No

– – – – – – Y

No.

MEMOBUS/

Modbus

Address

Name

Digital Operator Display

Description

Range

Default

Value

Change

During

Run

Control Method/

Access Level

P1-01

0600h

Output Voltage Setpoint
Output V Setpt

Sets the voltage that the output voltage regulator
will try and seek if H3-02, H3-06 and H3-10 are
not set to "21".

0.0 to 600.0

460.0 Vac

Yes

– – – – – – Y

P1-02

0601h

Output Voltage PID Gain
Output V Gain

Sets the responsiveness of the output voltage
regulator.
Higher = more responsive

0.0 to 25.00

1.00

Yes

– – – – – – Y

P1-03

0602h

Output Voltage PID Integral Time
Output V I Time

Sets the responsiveness of the output voltage
regulator.
Lower = more responsive

0.00 to 360.00

1.00 sec

Yes

– – – – – – Y

± ± ±

<

± ±

<

&/930

2/930

$2/930

&/9

2/9

9) Z 3*