Iqpump 7 ac drive, Simplex quick start procedure, Page 2 of 4 – Yaskawa iQpump 7 AC Drive User Manual

Page 2

background image

Parameter

Value

Description

Reference

Comments

E2-01

Drive Size

Dependent

Motor Rated Current

Set to the motor nameplate full load amps.

For submersible motors use service
factor amps (SFA).

E2-04

2

Number of Motor Poles

Number of motor poles is used to show the correct motor RPM on the display

Enter ’4’ for an 1800 RPM motor and ‘2’ for a 3600 RPM motor.

Confirm number of poles

2 Pole Motor = 3600 RPM

4 Pole Motor = 1800 RPM

6 Pole Motor = 1200 RPM

8 Pole Motor = 900 RPM

P1-03

145

Feedback Device
Scaling

System Scaling: Enter feedback device maximum:

Example: Enter 200 for pressure transducer with a maximum of 200 PSI at 20mA.

Confirm feedback device scaling.

(See Illustration 1)

d1-01

0

Set-Point 1

Set System Set-Point

Set to system pressure

P1-04

0.0 PSI

Start Level

When the iQpump is turned On and the feedback signal level (transducer) falls below this

level, the pump system will start after the time specified in P1-05 (default 1 sec).

Programming the Start Level as an Absolute Value

Start Level has to programmed to a positive value in order for the Start Level to be an

absolute value. Example: Start Level P1-04 set to 50 PSI and delay time P1-05 set to

5 sec. Pump system will start when the pressure drops below 50 PSI for 5 sec.

Programming the Start Level as a Delta Level from the System Set-Point

Start Level has to programmed to a negative value in order for the Start Level to be a

delta value from the set-point.

Example: Start Level P1-04 set to –10 PSI with a system set-point of 50 PSI and a delay

time P1-05 set to 5 sec. Pump system will start when the pressure drops below 40 PSI

(50 - 10) for 5 sec.

It is mandatory to program the Start Level

in order to use the sleep function.

(See Illustration 2 and 3)

P1-06

40.0 Hz

Minimum Pump
Frequency

Minimum speed (Hz) the pump motor has to operate at.

Example: Base pump motor speed is 3600 RPM, minimum speed is 2400 RPM. Set

minimum pump frequency to 40.0 Hz. (2400 ÷ 3600 x 60 Hz = 40 Hz)

Minimum pump frequency should be set to

a value where the pump enters a no-flow

condition.

P4-10

0

Disabled

Auto Mode Operator
Run Power Down
Storage

Stores the run status in the Auto mode when operating from digital operator (b1-02=0).
0: Disabled
1: Enabled

Recommended for use when Start/Stop

command is from keypad.

(See Illustration 6)

P5-04

1

Enabled

Hand Key
Enable / Disable

Enables or disables the Hand Key on the digital operator.
0: Disabled
1: Enabled

Hand Key on keypad.

(See Illustration 4)

START LEVEL

Examples:

0 – 1000, no decimals, P1-03 = 1000

0 – 300.0, one decimal, P1-03 = 10300

0 – 50.00, two decimals, P1-03 = 25000

P1-03 = 0 0 0 0 0 Feedback Scaling

Feedback
Maximum

Decimal Point

Position

TRANSDUCER / FEEDBACK DEVICE SCALING

Start Pump System

Start

Delay

200 PSI

Start Level P1-04 (Absolute)
(Example 100 PSI)

System Set-Point
(Example 150 PSI)

Feedback Signal from

pressure transducer

(4 – 20 mA)

0

Time

Pressure

Start Level Delay (P1-05)

(Example 5.0 sec.)

Feedback Scaling (P1-03)
(Example 200 PSI)

SLEEP MODE (Example)

Minimum Speed P1-06
(Example 40.0 Hz)

Output

Frequency

(pump motor

speed)

0

Sleep Delay Time (P2-03)

(Example 5.0 sec.)

Ramp or Coast to Stop, b1-02

Output Frequency

60 Hz

Pump Running

Go to Sleep

Time

WAIT FOR PRESSURE TO FALL BELOW

START LEVEL (P1-04)

WAIT

SYSTEM STARTS WHEN

PRESSURE SIGNAL

FALLS BELOW 100 PSI

SYSTEM GOES TO SLEEP

WHEN PUMP MOTOR SPEED

DROPS BELOW 2400 RPM

2

1

3

Start Pump System

Start

Delay

200 PSI

System Set-Point
(Example 150 PSI)

Feedback Signal from

pressure transducer

(4 – 20 mA)

0

Time

Pressure

Start Level Delay (P1-05)

(Example 5.0 sec.)

Feedback Scaling (P1-03)
(Example 200 PSI)

WAIT

SYSTEM STARTS WHEN

PRESSURE SIGNAL

FALLS BELOW 100 PSI

Start Level P1-04 (Delta)
(Example -50 PSI,
Start Level = 150 – 50 = 100 PSI)

Example: Absolute Level (Positive Start Level)

Example: Delta Level (Negative Start Level)

Note: When System Set-point is changed, the start level is automatically adjusted.

-50 PSI

100 PSI

100 PSI

150

150

Step

5

iQpump Quick Setup Parameter Overview (Simplex)

Use to change the sign.

Page 2 of 4

iQpump 7 AC Drive

(Software 0034)

Simplex Quick Start Procedure