Speed command operation parameter is set correctly, Correct and unique network address, Troubleshooting – a - 7 – Yaskawa P7 Metasys N2 User Manual
Page 45

Troubleshooting – A - 7
Speed Command Operation Parameter Is Set Correctly
The speed command operation parameter needs to be set for “Serial Com”.
Table A.2 - Speed Command Operation Parameter
Parameter Number
Setting Choices
Setting Descriptions
0 Operator
1 Terminals
2
Serial Com (Metasys N2)
b1-01
3 Option
PCB
Correct and Unique Network Address
Each device on a Metasys N2 network requires its own unique address. The drive also needs to be programmed to accept the Metasys N2
protocol.
Table A.3 - Serial Communication Device Address Parameter
Parameter Number
Setting Range
Setting Description
H5-01
0 to FFh (0 to 255 dec)x
Serial communication device address
H5-08
0 to 2
1: N2 (Metasys)