Metasys n2 binary input (bi) summary, Metasys n2 binary output (bo) summary, Cable loss behavior 4-5 – Yaskawa P7 Metasys N2 User Manual
Page 29

Cable Loss Behavior 4-5
Metasys N2 Binary Input (BI) Summary
Table 4.3 – Metasys N2 Binary Input Summary (P7U to Metasys N2)
Object ID
Object Name
Default
Off (0) State
On (1) State
BI 1
RUN / STOP MONITOR
0
STOPPED
RUNNING
BI 2
FORWARD / REVERSE MONITOR
0
FORWARD
REVERSE
BI 3
DRIVE READY MONITOR
0
NOT READY
READY
BI 4
FAULT MONITOR
0
NOT FAULTED
FAULTED
BI 5
ZERO SPEED
0
NOT ZERO SPEED
ZERO SPEED
BI 6
SPEED AGREE
0
NOT SPEED AGREE
SPEED AGREE
BI 7
MINOR FAULT
0
NO MINOR FAULT
MINOR FAULT
BI 8
MAJOR FAULT
0
NO MAJOR FAULT
MAJOR FAULT
BI 9
DRIVE COMMUNICATION
ERROR MONITOR
0 NO
ERROR
ERROR
BI 10
MULTI-FUNCTION OUTPUT 1 (H2-01)
0
- -
BI 11
MULTI-FUNCTION OUTPUT 2 (H2-02)
0
-
-
BI 12
MULTI-FUNCTION OUTPUT 3 (H2-03)
0
-
-
BI 13
SAFETY INTERLOCK MONITOR
0
SAFETY CLEAR
TERMINAL 3 CLOSED
SAFETY SET
TERMINAL 3 OPEN
BI 14
HAND / AUTO REFERENCE MONITOR
0
REMOTE
LOCAL
BI 15
MULTI-FUNCTION INPUT 1 MONITOR
0
OFF
ON
BI 16
MULTI-FUNCTION INPUT 2 MONITOR
0
OFF
ON
BI 17
MULTI-FUNCTION INPUT 3 MONITOR
0
OFF
ON
BI 18
MULTI-FUNCTION INPUT 4 MONITOR
0
OFF
ON
BI 19
MULTI-FUNCTION INPUT 5 MONITOR
0
OFF
ON
Metasys N2 Binary Output (BO) Summary
Table 4.4 – Metasys N2 Binary Output Summary (Metasys N2 to P7U)
Object ID
Object Name
Default
Off (0) State
On (1) State
BO 1
RUN FORWARD COMMAND
0
STOP
FORWARD
BO 2
RUN REVERSE COMMAND
0
STOP
REVERSE
BO 3
SERIAL FAULT (EF0) COMMAND
0
NO FAULT
FAULT
BO 4
FAULT RESET COMMAND
0
NO RESET
RESET
BO 5
MULTI-FUNCTION INPUT 1 (H1-01)
0
-
-
BO 6
MULTI-FUNCTION INPUT 2 (H1-02)
0
-
-
BO 7
MULTI-FUNCTION INPUT 3 (H1-03)
0
-
-
BO 8
MULTI-FUNCTION INPUT 4 (H1-04)
0
-
-
BO 9
MULTI-FUNCTION INPUT 5 (H1-05)
0
-
-
BO 10
PANEL LOCK
0
LOCAL/REMOTE AND
STOP/RESET KEYS
ENABLED
LOCAL/REMOTE AND STOP/RESET
KEYS DISABLED
BO 11
COMMUNICATION FAULT ENABLE
0
EF0 NOT ACTIVATED IF
CABLE LOSS OCCURS
EF0 ACTIVATED IF CABLE LOSS
OCCURS