Installation 1-7, H5-01 = 1f, H5-02 = 3 – Yaskawa P7 Metasys N2 User Manual
Page 13

Installation 1-7
Table 1.2 - Drive Programming Procedure for Metasys N2
Description
Key Operation
Digital Operator Display
x7
Select Node Address
Press the DOWN ARROW key until parameter 
H5-01 is displayed (01 blinking). Press the DATA 
ENTER key to edit parameter H5-01 (value 
blinking). Press the RESET or RIGHT ARROW 
key to select the digit to edit. The selected digit 
will blink. Press the UP ARROW or DOWN 
ARROW keys to change the value of the selected 
digit until the correct value is displayed. Press the 
DATA ENTER key to accept the entry. Edit all 
digits prior to pressing the DATA ENTER key. 
“Entry Accepted” will be displayed if successful. 
-ADV-
Serial Comm Adr
- - - - - - - - - - - - - - - - - - - - - - - - - -
H5-01 = 1F*
(0~255)
“1F”
 
 
 
*This is always entered as a hexadecimal 
value. Refer to the conversion chart in 
Appendix B for information on converting 
decimal values to their hexadecimal equivalents
Select Baud Rate of 4800 Baud
Press the UP ARROW key until parameter H5-02 
is displayed (02 blinking). Press the DATA 
ENTER key to edit parameter H5-02 (value 
blinking). Press the UP ARROW key to change 
the parameter value until the display matches the 
display shown on the right. Press the DATA 
ENTER key to accept the entry. “Entry Accepted” 
will be displayed if successful.
-ADV-
Serial Baud Rate
- - - - - - - - - - - - - - - - - - - - - - - - - -
H5-02 = 3
*3*
9600 Baud
“3”
Select The Drive Mode
-DRIVE-
** Main Menu **
- - - - - - - - - - - - - - - - - - - - - - - - - -
Operation
Enter The Drive Mode
-DRIVE-
Rdy
Frequency Ref
U1-01 =
0.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - -
U1-02
=
0.00Hz
U1-03
=
0.00A