YASKAWA ELECTRIC TOBP C710606 21E YASKAWA AC Drive - V1000 Finless Installation Guide
Table 5 Correct Installation Spacing
NOTICE: Do not install V1000 Finless drives using the Side-by-Side method available in standard V1000
drive models. Improper drive cooling may result in damage to the drive. Install V1000 Finless drives with a
minimum side-by-side clearance of 30 mm (1.18 in).
■
Ambient Temperature Derating
Parameters L8-12 (Ambient Temperature Setting) and L8-35 (Installation Method Selection)
must be set according to the installation conditions if the ambient temperature is higher than
35
for drive derating according to ambient temperature.
Parameter L8-12 = 40
°C (default). The setting range is -10 to 50°C.
Operating the V1000 Finless drive between -10 and 35
°C allows 100% continuous current
without derating. Drive operation between 35 and 50
°C requires drive derating according to
.
The drive can be used with 100% rating between -10 and 50
°C ambient temperature if the
airflow around the unit is 0.5 m/s or more. In this case set L8-35 = 0 (Installation method =
IP20 standard drive).
Figure 4
Figure 5 Ambient Temperature and Drive Derating
Voltage Class
Drive Model
CIMR-V
Side Clearance (a)
mm / (in)
Single-Phase 200 V Class
BA0001 to BA0012
30 / (1.18)
Three-Phase 200 V Class
2A0001 to 2A0069
Three-Phase 400 V Class
4A0001 to 4A0038
0
Rating
100%
80%
35°C
L8-35 = 3 (default)
Finless/External heatsink
50°C
L8-12
Ambient
Temperature
Setting
L8-35 = 0
surrounding
airflow of 0.5 m/s