beautypg.com

Vsd network variables, 7 network variables – Yaskawa SI-W3 User Manual

Page 31

background image

7 Network Variables

YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide

31

VSD Network Variables

VSD Network Input Variables

VSD Network Output Variables

Name

Variable Type

Description

nviDrvSpeedStpt

SNVT_switch

Drive Speed Setpoint

nviInvSetFreq

SNVT_freq_hz

Drive Frequency Reference (Hz)

nviDrvSpeedRef

SNVT_lev_percent

Drive Speed SetFreq (%)

nviRunCommand

SNVT_switch

Drive Run Reference

nviOpCommands

SNVT_state

Drive Operation Commands

nviDrvSpeedScale

SNVT_lev_percent

Drive Speed Setpoint Scaling

nviEmergOverride

SNVT_hvac_emerg

Drive Emergency

nviFltRstCommand

SNVT_switch

Drive Speed Setpoint Scaling

nviDrvEnergyClr

SNVT_switch

Drive Speed Setpoint Scaling

nviReadParamNum

SNVT_count

Drive Parameter Read

nviWriteParamNum

SNVT_count

Drive Parameter Write

nviWriteParamVal

SNVT_count_inc

Drive Parameter Write Data

Name

Variable Type

Description

nvoDrvSpeed

SNVT_lev_percent

Drive Speed Feedback (%)

nvoRunStatus

SNVT_switch

Drive Run Status

nvoInvOutFreq

SNVT_freq_hz

Drive Output Frequency

nvoDrvCurrent

SNVT_amp

Drive Output Current

nvoDrvVolt

SNVT_volt

Drive Output Voltage

nvoDCBUS

SNVT_volt

Drive DC Voltage

nvoDrvPwr

SNVT_power_kilo

Drive Output Power

nvoDrvEnergy

SNVT_elec_kwh_l

Cumulative Drive Energy

nvoDrvRunHours

SNVT_time_hour

Drive Total Running Hours

nvoInvFault

SNVT_switch

Drive Fault Status

nvoInvAlarm

SNVT_switch

Drive Alarm Status

nvoReadParamVal

SNVT_count_inc

Drive Parameter Read Data

nvoParamErr

SNVT_count

Drive Parameter Error

nvoSpdStptFb

SNVT_lev_percent

Drive Speed Setpoint Feedback1

nvoSpdCmd

SNVT_lev_percent

Drive Speed Setpoint Feedback2

nvoDrvStatus

SNVT_state

Drive Status

nvoFltstatus1

SNVT_state

Drive Fault Status1

TOBP_C730600_56A_0_0_E.fm 31 ページ 2011年11月2日 水曜日 午後6時10分