Refer to, Table a.3, Table a.4 – Yaskawa RC5 Converter User Manual
Page 65

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
65
Table A.3 Multi-function Input Functions
Table A.4 Multi-function Output Functions
Setting Value
Function
(H1-01, 02)
Remarks
8
External baseblock (NO contact)
[Ext BaseBlk N.O.]
9
External baseblock (NC contact)
[Ext BaseBlk N.C.]
F
Not used
[Term Not Used]
14
Fault reset
[Fault Reset]
24-2F
External fault
[External Fault]
24: External Fault, Normally Open, Always Detected, Coast To Stop
25: External Fault, Normally Closed, Always Detected, Coast To Stop
26: External Fault, Normally Open, During Run, Coast To Stop
27: External Fault, Normally Closed, During Run, Coast To Stop
28: External Fault, Normally Open, Always Detected, Fast Stop
29: External Fault, Normally Closed, Always Detected, Fast Stop
2A: External Fault, Normally Open, During Run, Fast Stop
2B: External Fault, Normally Closed, During Run, Fast Stop
2C: External Fault, Normally Open, Always Detected, Alarm Only
2D: External Fault, Normally Closed, Always Detected, Alarm Only
2E: External Fault, Normally Open, During Run, Alarm Only
2F: External Fault, Normally Closed, During Run, Alarm Only
Setting value
Function
(H2-02, 03)
Remarks
0
During run
[During RUN 1]
Closed = When a run command is input or the Unit is outputting voltage.
6
Regenerative unit ready
[Regen Unit Ready]
Closed = When the Unit is powered up, not in a fault state, and in the DRIVE
mode.
7
During DC bus undervoltage (UV) detection
[DC Bus Undervolt]
Closed = When the DC bus voltage falls below the UV trip level set in L2-05.
8
During baseblock
[BaseBlk 1]
Closed = When the Unit is not outputting voltage.
A
During MCON
[Mc On]
Closed = When the pre-charge contactor contact is energized.
E
Fault
[Fault]
Closed = When the Unit experiences a major fault.
F
Not used
[Not Used]
10
Alarm
[Minor Fault]
Closed = When the Unit experiences an alarm.
11
Fault reset command active
[Reset Cmd Active]
Closed = When the Unit receives a reset command from a digital input terminal or
serial communication.
1E
Restart enabled
[Restart Enabled]
Closed = When the Unit is performing an automatic restart attempt. Automatic
restart is configured by parameter L5-01.
1F
Overload (OL1) pre-alarm
[Overload (OL1)]
Closed = When OL1 is 80% of its trip point or greater.
20
Overheat pre-alarm
[OH Prealarm]
Closed = When the Unit’s heatsink temperature exceeds the setting of parameter
L8-02.