3.4 Wiring Main Circuit Terminals
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
29
3.4
Wiring Main Circuit Terminals
◆
Required Wire Size
Select wires to be used for wiring from
and
Table 3.4 200 V Class Wire Size
Note: Cable size is selected assuming external wiring of single 3-core cables at an ambient temperature of 30°C.
Note: For model number 2015, use closed-loop connectors that are recommended by JST (JST 14-5).
Circuit
RC5
CIMR-R5U
Terminal Symbol
Terminal
Screw
Wire Size
<1> Wire size is determined by 75°C temperature-rated copper wire.
Wire Type
mm
2
AWG
Main
23P7
R/L1, S/L2, T/L3, (+), (+), ,
M4
2 to 5.5
14 to 10
Power cable: 600 V
vinyl sheathed wire or
equivalent
r1/ 11, 1/ 21,
t1/ 31
25P5
R/L1, S/L2, T/L3, (+), (+), ,
M4
3.5 to 5.5
12 to 10
r1/ 11, 1/ 21, t1/ 31
2 to 5.5
14 to 10
3.5 to 5.5
12 to 10
27P5
R/L1, S/L2, T/L3, (+), (+), ,
M4
5.5
10
r1/ 11, 1/ 21, t1/ 31
2 to 5.5
14 to 10
3.5 to 5.5
12 to 10
2011
R/L1, S/L2, T/L3, (+), (+), ,
M5
8
8
r1/ 11, 1/ 21, t1/ 31
2 to 5.5
14 to 10
5.5 to 8
10 to 8
2015
R/L1, S/L2, T/L3, (+), (+), ,
M5
8
8
r1/ 11, 1/ 21, t1/ 31
2 to 5.5
14 to 10
5.5 to 8
10 to 8
2018
R/L1, S/L2, T/L3, (+), (+), ,
M8
22
4
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
2022
R/L1, S/L2, T/L3, (+), (+), ,
M8
22
4
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
2030
R/L1, S/L2, T/L3, (+), (+), ,
M8
30 to 38
3 to 2
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
14
6
2037
R/L1, S/L2, T/L3, (+), (+), ,
M8
50 to 60
1 to 1/0
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
14
6
Control
Common to all models
S1, S2, S3, S4, SS, SP, SC, M1, M2, M3, M4,
MA, MB, MC, AM, AC
—
twisted wire
0.5 to 1.25
single
0.5 to 1.25
twisted wire
20 to 16
single
20 to 16
Shielded twisted-pair
wires
E (G)
M3.5
0.5 to 2
20 to 14