3.4 Wiring Main Circuit Terminals
30
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Table 3.5 400 V Class Wire Size
Note: Cable size is selected assuming external wiring of single 3-core cables at an ambient temperature of 30°C
Note: For model number 4011 and 4015, use closed-loop connectors that are recommended by JST (JST 3.5 - R5).
Circuit
RC5
CIMR-R5U
Terminal Symbol
Terminal
Screw
Wire Size
<1> Wire size is determined by 75°C temperature-rated copper wire.
Wire Type
mm
2
AWG
Main
43P7
R/L1, S/L2, T/L3, (+), (+), (+), ,
M4
2 to 5.5
14 to 10
Power cable:
600 V vinyl
sheathed wire or
equivalent
r1/ 11, 1/ 21,
t1/ 31
45P5
R/L1, S/L2, T/L3, (+), (+), (+), ,
M4
2 to 5.5
14 to 10
r1/ 11, 1/ 21,
t1/ 31
47P5
R/L1, S/L2, T/L3,
(+), (+), ,
M4
2 to 5.5
14 to 10
r1/ 11, 1/ 21,
t1/ 31
4011
R/L1, S/L2, T/L3,
(+), (+), ,
M5
3.5 to 5.5
12 to 10
r1/ 11, 1/ 21,
t1/ 31
2 to 5.5
14 to 10
4015
R/L1, S/L2, T/L3, (+), (+), ,
M5
5.5
10
r1/ 11, 1/ 21, t1/ 31
2 to 5.5
14 to 10
5.5
10
4018
R/L1, S/L2, T/L3, (+), (+), ,
M6
8 to 14
8 to 6
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
4022
R/L1, S/L2, T/L3, (+), (+), ,
M6
8 to 14
8 to 6
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
4030
R/L1, S/L2, T/L3, (+), (+), ,
M6
14
6
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
4037
R/L1, S/L2, T/L3, (+), (+), ,
M6
14 to 22
6 to 4
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
4045
R/L1, S/L2, T/L3, (+), (+), ,
M8
22 to 38
4 to 2
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
8
8
4055
R/L1, S/L2, T/L3, (+), (+), ,
M8
38 to 60
2 to 1/0
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
14
6
4075
R/L1, S/L2, T/L3, (+), (+), ,
M8
50 to 60
1 to 1/0
r1/ 11, 1/ 21, t1/ 31
M4
2 to 5.5
14 to 10
M6
14
6
Control
Common to all
models
S1, S2, S3, S4, SS, SP, SC, M1, M2, M3, M4, MA,
MB, MC, AM, AC
—
twisted wire
0.5 to 1.25
single
0.5 to 1.25
twisted wire
20 to 16
single
20 to 16
Shielded
twisted-pair wires
E (G)
M3.5
0.5 to 2
20 to 14