6 related drive parameters – Yaskawa Modbus TCP/IP SI-EM3D/V User Manual
Page 32

No.
(Addr.
Hex)
Name
Description
Values
F7-15
(03F3)
Communication Speed
Selection
Sets the communication speed
0: 10 Mbps
10: 10 Mbps
100: 100 Mbps
101: 10 (Port 1)/100 Mbps (port 2)
102: 100 (Port 1)/10 Mbps (port 2)
Default: 10
<10>
Range: 10; 100 to
102
<10>
F7-16
(03F4)
Communication Loss
Timeout
Sets the timeout value for communication loss detection in
tenths of a second. A value of 0 disables the connection
timeout.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0.0
Min.: 0.0
Max.: 30.0
H5-11
(043C)
Communications
ENTER Function
Selection
Selects the function for the ENTER command that saves
parameter data to the drive.
0: Parameter changes are activated when ENTER command
is written
1: Parameter changes are activated immediately without use
of ENTER command
Default: 1
Range: 0, 1
<1>
To start and stop the drive with the master device using serial communications, set b1-02 to 3. To control the
drive frequency reference of the drive via the master device, set b1-01 to 3.
<2>
When set to 3, 4, or 5, the drive will continue to operate when a fault is detected. Take safety measures, such as
installing an emergency stop switch.
<3>
Available in drive software versions PRG: 1024 and later.
<4>
Parameter setting value is not reset to the default value when the drive is initialized.
<5>
Cycle power for setting changes to take effect.
<6>
When F7-13 is set to 0, parameters F7-01 to F7-12 must be set, and all IP Addresses (as defined with parameters
F7-01 to F7-04) must be unique.
<7>
When F7-14 is set to 0 or 2, parameter F7-15 must be set.
<8>
Default setting differs depending on drive software version. PRG: 1012 to 1015: 0
PRG: 1016 and later: 1
<9>
Setting range differs depending on drive software version. PRG: 1012 to 1023, Range: 0 to 2
PRG: 1024 and later, Range: 0 to 8
<10>
Setting values differ depending on drive software version. PRG: 1012 to 1015, Default: 0; Range: 0, 10, 100
PRG: 1016 to 1023, Default: 10; Range: 10, 100
PRG: 1024 and later, Default: 10; Range: 10; 100 to 102
Table 7 Option Monitors
No.
Name
Description
Value Range
U6-80
to
U6-83
Online IP Address
IP Address currently available; U6-80 is the most significant
octet
0 to 255
U6-84
to
U6-87
Online Subnet
Subnet currently available; U6-84 is the most significant octet 0 to 255
6 Related Drive Parameters
32
YASKAWA TOEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Installation Manual