New parameters and new monitor, H2: multi-function digital outputs, I.2 new parameters and new monitor – Yaskawa AC Drive Z1000 AC Drive Bypass for HVAC User Manual
Page 5

i.2
New Parameters and New Monitor
u
H2: Multi-Function Digital Outputs
Note:
H2-oo parameters are available in bypass controller software versions VST800298 and later.
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection
The bypass has three multi-function output terminals.
lists the functions available for these terminals using H2-01,
H2-02, and H2-03.
No.
Addr.
Hex
Parameter Name
Setting Range
Default
H2-01
(040B)
Terminal M1-M2 Function Selection (relay)
0 to 160
0: During Run 1
H2-02
(040C)
Terminal M3-M4 Function Selection (relay)
0 to 160
1: Zero Speed
H2-03
(040D)
Terminal M5-M6 Function Selection (relay)
0 to 160
2: Speed Agree 1
Table i.2 Multi-Function Digital Output Terminal Settings
Setting
Function
Page
0
During Run 1
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock 1 (N.O.)
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
13
Speed Agree 2
Setting
Function
Page
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1A
During Reverse
1B
During Baseblock 2 (N.C.)
1E
Restart Enabled
20
Drive Overheat Pre-Alarm (oH)
2F
Maintenance Period
37
During Run 2
39
Watt Hour Pulse Output
3D
During Speed Search
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
60
Internal Cooling Fan Alarm
100 to 160 Functions 0 to 60 with Inverse Output
Setting 0: During Run
The output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure i.1 During Run Time Chart
i.2 New Parameters and New Monitor
YASKAWA TOEP YAISUP 06A YASKAWA AC Drive – Z1000 Bypass Manual Supplement
5