New and modified faults and alarms, New faults and alarms, Modified fault – Yaskawa AC Drive Z1000 AC Drive Bypass for HVAC User Manual
Page 20: I.5 new and modified faults and alarms

i.5
New and Modified Faults and Alarms
u
New Faults and Alarms
Note:
Faults and alarms in this section are added in bypass controller software version VST800298.
HOA Keypad Display
Minor Fault Name
AL16
Input Phase Rotation
Cause
Possible Solution
Incorrect phase rotation while Z1-52 is set to 1 in
Bypass Mode.
Check the sequence (phase rotation) of the input wiring to the bypass package.
HOA Keypad Display
Fault Name
FB15
Input Phase Loss
Cause
Possible Solutions
Bypass Mode current unbalance condition
exceeded the unbalance level limit set by Z1-50 for
the amount of time specified in Z1-51.
• Check input wiring including fuses, breakers, connections, upstream from the bypass.
• Check the motor wiring and connections.
HOA Keypad Display
Fault Name
FB16
Input Phase Rotation
Cause
Possible Solution
Incorrect phase rotation while Z1-52 is set to 2 in
Bypass Mode.
Check the sequence (phase rotation) of the input wiring to the bypass package.
u
Modified Fault
HOA Keypad Display
Fault Name
CE
MEMOBUS/ Modbus Communication Error
Cause
Possible Solution
Communications between the bypass controller
and the drive have stopped for longer than 2
seconds.
Note:
Added in bypass controller software
version VST800298.
Check the communication cable, terminal CN6 on the bypass board, and terminals R+, R-, S+, and
S- on the drive terminal strip.
Note:
This fault may also occur when the bypass is initialized by setting Z1-01 to 1, 2, or 3.
Cycle power on the bypass to clear.
i.5 New and Modified Faults and Alarms
20
YASKAWA TOEP YAISUP 06A YASKAWA AC Drive – Z1000 Bypass Manual Supplement