2. Set H3-10 to “1F - HAND Mode” when using Terminal A2 for HAND Mode frequency reference.

n

Z1-50: Bypass Unbalanced Current Detection Level

Sets the current unbalance level between phases as a percentage of parameter E2-01 when operating in Bypass Mode. This

function is used in conjunction with parameter Z1-51 to detect input or output phase loss during bypass operation.
The unbalance level is determined by measuring the RMS current in each of the output phases. The amount of current unbalance

between the phases is calculated using the following formula:
Unbalance Level = (I

(max)

- I

(min)

) / I

(max)

× 100%

When the unbalance level exceeds the Z1-50 setting for longer than the time set to Z1-51, an “FB15 – Input Phase Loss” fault

is triggered and the drive will coast to stop.
This parameter rarely needs to be changed.

Note:

Parameter available in bypass controller software versions VST800298 and later.

No.

Addr. Hex

Name

Setting Range

Default

Z1-50

(85F7)

Bypass Unbalanced Current Detection Level

5.0 to 50.0%

25.0%

n

Z1-51: Bypass Unbalance Trip Time Detection Level

Sets the trip time for an unbalance condition when operating in Bypass Mode. This function is used in conjunction with

parameter Z1-50 to detect input or output phase loss during bypass operation.

Note:

1. Parameter available in bypass controller software versions VST800298 and later.
2. Setting this parameter to 0.0 will disable unbalance (bypass phase loss) protection.

No.

Addr. Hex

Name

Setting Range

Default

Z1-51

(85F8)

Bypass Unbalance Trip Time Detection Level

0.0 to 30.0 s

5.0 s

n

Z1-52: Bypass Phase Rotation

Input phase rotation is ignored when operating in Drive Mode. Input phase rotation determines motor direction when operating

in Bypass Mode.
If input phase rotation is reversed and this parameter is set to 1, an “AL16 – Inp Phase Rotation” alarm will be displayed when

operation starts in Bypass Mode and operation continues.
If input phase rotation is reversed and this parameter is set to 2, an “FB16 – Inp Phase Rotation” fault will be displayed when

operation starts in Bypass Mode and the drive will coast to stop.
Controls the behavior of the bypass phase rotation detection when operating in Bypass Mode.

Note:

Parameter available in bypass controller software versions VST800298 and later.

No.

Addr. Hex

Name

Setting Range

Default

Z1-52

(85F9)

Bypass Phase Rotation

0 to 2

1

Setting 0: Disabled
Setting 1: Alarm
Setting 2: Fault

i.2 New Parameters and New Monitor

14