VS-616PC5/P5 Option Instruction Manual: Isolated Monitor Card CM-B2/P

INTERCONNECTION DIAGRAM

Fig. 4 shows the mounting and interconnection between the inverter and the Isolated Monitor Card
CM-B2/P.

WIRING NOTES

1. Separate the wires for output signals (from the Isolated Monitor Card’s terminal block TB1) from

the main circuit wires and other power cables.

2. Use a shielded wire to connect output signals. Connect the wire as shown in Fig. 5 to prevent

noise interference.

Failure to observe these precautions may result in equipment malfunctions.

L1 (R)

L2 (S)

L3 (T)

IM

U (T1)

V (T2)

W (T3)

VS-616/PC5/P5

E (G)

AC

AM

2

1

2CN

2CN

E

Isolated Monitor Card

CM-B2/P

Fig. 4 Interconnection Diagram

250

?

P

Current

Output

TB1

TP1

TB2

12

!

CAUTION

Shielded Sheath

Armor

Fig.5 Shielded Wire

B

C

A

A. NEVER connect the wire’s shielded sheath when

connecting wires.

B. WRAP insulating tape around shielded areas and

wires where termination occurs.

C. CONNECT the shielded wire end to the Ground-

ing Terminal (E) on the inverter’s Terminal E (G).