Yaskawa MicroTrac Gateway to Allen-Bradley Data Highway Plus for use with Microtrac LAN User Manual
Page 7

Introduction
7
Drive Description
4
OPERATION
PLC Gateway Status
The PLC gateway status is displayed on the four (4) character alphanumeric
display that is mounted on the CPU card.
The following is a list of the different status messages that may be displayed
and their meanings:
DISPLAY
MEANING
PUP
Initial power-up is OK.
WAIT
PLC communication speed not yet determined.
57KB
PLC communication speed is 57.6K baud..
115K
PLC communication speed is 115.2K baud.
ENOA
Error in Numeric Output Allocation.
ELIA
When the PLC gateway receives a logical input allocation
message, this error message could appear because the internal
allocation table is full and cannot handle another allocation.
The allocation table has room for 1024 allocations. A logical
allocation uses 1 element in the table.
EPMA
Port or Memory Address Error in loading software into
5136-SD interface card. This is caused by a missing or
inproperly installed card or inproper switch settings on the
5136-SD interface card.
EZ80
Z80 microprocessor on the 5136-SD interface card did not
start up properly. Probable cause would be a defective
5136-SD Interface card.
ENMI
Non-Maskable Interrupt Error on CPU card. Probable cause
could be electrical noise (EMI) near the PLC gateway chassis.
PLC Gateway
Status
RD 906-20
© 1994 MagneTek, Inc.
94-04