Introduction

4

Drive Description

2

HARDWARE

5136-SD Direct-Link Interface Card

The node number for the PLC gateway will normally be 200; however, check
the system schematic for confirmation. Occasionally a different node number
might be used.

This card may be installed into any half-size slot of the back plane.

A BNC type “T” connector is used to interconnect this board to the MicroTrac
LAN’s coaxial cable. A 93 ohm terminator must be placed at each end of the
coaxial cable (either a BNC terminator cap or connection to a LAND port).
The BNC “T” connector and 93 ohm terminator are identified below:

1. BNC “T” connector, 50 ohm impedance, MagneTek part number
05P00034-0540.

2. 93 ohm BNC terminator, MagneTek part number 05P00034-0586.

Set the I/O port address to 250H and all interrupts to off by setting the bit
switches on SW1 as shown in Table 4:

The Direct-Link Interface card in the Bridge must be connected to the Direct-
Link Interface card in the computer. Use two-conductor shielded cable as
shown on the system schematic.

5136-SD

Direct-Link

Interface Card

Table 4. Direct-Link Interface Card DIP Switch SW1 Settings

1

2

3

4

5

6

7

8

OFF

OFF

OFF

ON

OFF

ON

OFF

ON

RD 906-20