PLC Gateway Status

4/12/94

The PLC gateway status is displayed on the four (4) character alphanumeric
display that is mounted on the CPU card. Messages which are displayed are
shown in Table 7.

PLC Gateway

Status

Table 7. PLC Gateway Display Messages

MESSAGE

DESCRIPTION

TROUBLESHOOTING

BROM

This message will appear only when a MagneTek TI
Gateway ROM Configuration is used. If the firmware
does not see the correct configuration string in the
EPROM socket memory address, it ignores the con-
tents of the socket. If a valid configuration string
is found at the start of the EPROM, the remainder
of the EPROM configuration information is checked.
If the remaining configuration lines contain an
invalid base. slot, or module type, the firmware
displays the "BROM" on the 4 character display
and halts,

EARC

This message is displayed during PLC Gateway
initialization if the MicroTrac Network Interface card
is not found. Initialization is not completed.

ECdd

This indicates that the PLC Gateway is unable to

Check the cabling between the

get a configuration from the Texas Instruments .

5136-TI card and the TI RBC

PLC for base "dd"

Processor. Is the Texas Instruments
PLC on and has it been programmed?

When the PLC Gateway receives an allocation

Check the configuration and solve

message (0x10, 0x11, 0x12, 0x13, or 0x2D) from

tables that are loaded into the PLC.

the DSD LAN, it decodes the channel number into

Does the configuration include the

a base and slot number and attempts to get a

base being allocated? Is the base

configuration for that base from the Texas

being scanned? Check the solve

Instruments PLC. If it cannot, this error message

table. Is the base you are trying to

is displayed and the PLC Gateway hangs.

configure remote?

ECOM

This message appears during operation if the

Check the cabling between the

5136-TI card is not communicating with the

5136-TI card and the TI RBC

Texas Instruments PLC.

Processor. Check that the cable is
connected on 5136-TI card.

EIVA

When the PLC Gateway receives an allocation
message, it decodes the channel number into base
and slot numbers. If either of these numbers is
invalid, then this message is displayed. An alloca-
tion error message is returned to the sending node.

ELIA

When the PLC Gateway receives a logical input
allocation message, this error message could appear
because the internal allocation table is full and
cannot handle another allocation. The allocation
table has room for 1024 allocations. A logical
allocation uses 1 element in the table.

RD 3056-10