V7 EtherNet/IP Option Kit

CM093

18. Remove power from the V7 drive and wait for the charge lamp to be

completely extinguished. Wait at least five additional minutes for the V7 to
be completely discharged. Measure the DC bus voltage and verify that it is at
a safe level.

19. Reinstall the operator keypad and terminal cover.
20. Reapply power to the V7 drive.
21. Set parameters n003 and n004 to their appropriate values.

22. Resetting the V7 EtherNet/IP Option Kit to its defaults
The factory default settings are as follows:

Configure Network Parameters: DHCP
IP Address:

192.168.1.20

Subnet:

255.255.255.0

Gateway:

192.168.1.1

Gateway Usage: Disabled

Symptom: The V7 EtherNet/IP Option Kit main web page does not
display on the PC web browser screen.
Corrective Action: Check that the PC is set up, properly connected and
that an IP address has been assigned to both the node and DHCP server
and that they are both on the same local network.
If the web page is still not visible after confirming PC setup, then reset
the IP configuration of the V7 EtherNet/IP Option Kit to its factory
default as follows:

a. Remove power from the V7 drive and wait for the charge lamp to be

completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify that
it is at a safe level.

b. Slide the bottom Load Defaults (LD) switch (SW1) to the ON position.
c. Reapply power to the V7 and wait approximately 10 seconds for the

power-up cycle to complete.

Note: Additional wait time (approximately two minutes) may be
required if utilizing the DHCP feature of this card, and the DHCP
server is not available, or it did not respond to the request for an IP
address. The V7 EtherNet/IP Option Kit will indicate that the load
defaults process is complete when the MS/RUN LED is displaying a
steady GREEN status indication after the wait time.

d. Remove power from the V7 and wait for the charge lamp to be

completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify that
it is at a safe level. See the warning above.

e. Slide the bottom Load Defaults (LD) switch (SW1) to the OFF position.
f.

Reapply power to the V7 and wait approximately 10 seconds for the
power-up cycle to complete.

WARNING

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.

Address Parameter

Function

Data

Description

Default

103h

n003

Operation

Method

Selection

0

Operator Keypad

1

1

Terminal Strip

2

Built-in Modbus RTU

3

Option Kit (V7 EtherNet/IP

Option)

104h

n004

Reference

Selection

0

Operator Keypad

Potentiometer

2

1

Operator Keypad

2

Voltage Reference (0-

10VDC)

3

Current Reference (4-20mA)

4

Current Reference (0-20mA)

5

Pulse Train Reference

6

Built-in Modbus RTU

7

Multi-Function Analog Input

(0-10VDC)

8

Multi-Function Analog Input

(4-20mA)

9

Option Kit (V7 EtherNet/IP

Option)

198h

n152

Display

Scaling

0

0.01 Hz

0

1

0.1 %

2-39

RPM (Enter motor poles)

40-3999

User Setting

WARNING

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.