Yaskawa Electric America, Inc. –
IG.V7.26, Page 5 of 11
Date: 05/24/2010 Rev: 10-05
V7 EtherNet/IP Option Kit
CM093
18. Remove power from the V7 drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the V7 to
be completely discharged. Measure the DC bus voltage and verify that it is at
a safe level.
19. Reinstall the operator keypad and terminal cover.
20. Reapply power to the V7 drive.
21. Set parameters n003 and n004 to their appropriate values.
22. Resetting the V7 EtherNet/IP Option Kit to its defaults
The factory default settings are as follows:
Configure Network Parameters: DHCP
IP Address:
192.168.1.20
Subnet:
255.255.255.0
Gateway:
192.168.1.1
Gateway Usage: Disabled
Symptom: The V7 EtherNet/IP Option Kit main web page does not
display on the PC web browser screen.
Corrective Action: Check that the PC is set up, properly connected and
that an IP address has been assigned to both the node and DHCP server
and that they are both on the same local network.
If the web page is still not visible after confirming PC setup, then reset
the IP configuration of the V7 EtherNet/IP Option Kit to its factory
default as follows:
a. Remove power from the V7 drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify that
it is at a safe level.
b. Slide the bottom Load Defaults (LD) switch (SW1) to the ON position.
c. Reapply power to the V7 and wait approximately 10 seconds for the
power-up cycle to complete.
Note: Additional wait time (approximately two minutes) may be
required if utilizing the DHCP feature of this card, and the DHCP
server is not available, or it did not respond to the request for an IP
address. The V7 EtherNet/IP Option Kit will indicate that the load
defaults process is complete when the MS/RUN LED is displaying a
steady GREEN status indication after the wait time.
d. Remove power from the V7 and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify that
it is at a safe level. See the warning above.
e. Slide the bottom Load Defaults (LD) switch (SW1) to the OFF position.
f.
Reapply power to the V7 and wait approximately 10 seconds for the
power-up cycle to complete.
WARNING
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.
Address Parameter
Function
Data
Description
Default
103h
n003
Operation
Method
Selection
0
Operator Keypad
1
1
Terminal Strip
2
Built-in Modbus RTU
3
Option Kit (V7 EtherNet/IP
Option)
104h
n004
Reference
Selection
0
Operator Keypad
Potentiometer
2
1
Operator Keypad
2
Voltage Reference (0-
10VDC)
3
Current Reference (4-20mA)
4
Current Reference (0-20mA)
5
Pulse Train Reference
6
Built-in Modbus RTU
7
Multi-Function Analog Input
(0-10VDC)
8
Multi-Function Analog Input
(4-20mA)
9
Option Kit (V7 EtherNet/IP
Option)
198h
n152
Display
Scaling
0
0.01 Hz
0
1
0.1 %
2-39
RPM (Enter motor poles)
40-3999
User Setting
WARNING
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.