11. Diagnostic LED power up test sequence

A power-up test is performed each time the V7 drive is powered up after the
initial boot sequence. The initial boot sequence may take several seconds.
When this sequence is complete, the LEDs will assume normal conditions.

The EtherNet/IP Option Kit is successfully initialized after the LEDs have
completed the above sequence.

12. LED descriptions
The EtherNet/IP Option Kit LED status after the power-up sequence is described
below. Please wait at least five seconds for the loading process to complete before
verifying the status of the LEDs.

13. Connect to the V7 EtherNet/IP Option Kit

Note: It is strongly recommended that shielded CAT-5 cable be used.
a. Connect to the Ethernet network.

1. Direct connection: To connect directly to the V7 EtherNet/IP

Option Kit, plug one end of a shielded CAT-5 crossover cable into
the RJ-45 socket on the V7 EtherNet/IP Option Kit. Connect the
other end to the RJ-45 Ethernet socket on the configuration device,
typically a controller, laptop or other PC.

2. Connection through hub or switch: To connect through a switch,

hub or router, connect V7 EtherNet/IP Option Kit to the switch, hub
or router using a standard shielded CAT-5 patch cable.

b. Loop the CAT-5 Ethernet cable through the provided ferrite

(Intermark RFC-13) and connect the ferrite as close to the RJ-45
connection as possible. Secure the ferrite to the Ethernet cable with the
provided cable tie. If the ferrite cannot be mounted in your installation
please contact Yaskawa for application assistance. See the figure in the
lower right corner of this page.

c. Attach the provided ferrites to the V7 drive motor and power leads as

close to the V7 drive terminals as possible (typically within 1 foot).
Secure the ferrites to the motor and power leads with the provided cable
ties. See the figure to the right.

Successful Initialization:

The V7 EtherNet/IP Option Kit hardware is installed and operating correctly with
the LEDs in the states shown in bold text in the "LED Descriptions" table. The
LINK LED represents the status of the physical connection to the network and is
not indicative of any card state.

Application of Ferrites:

Seq

MS/RUN

NS/CON

Time

1

GREEN

OFF

250ms

2

RED

OFF

250ms

3

GREEN

OFF

250ms

4

GREEN

GREEN

250ms

5

GREEN

RED

250ms

6

GREEN

OFF

Seq

MS/RUN

MS/RUN

GREEN – Card Functioning Normally
GREEN BLINK – Standby/Initializing (500ms cycle)
RED BLINK – Minor Fault (500ms cycle)
RED – Major Fault
GREEN/RED BLINK – Module Test (500ms cycle)

NS/CON

GREEN – Connected
GREEN BLINK – Waiting for Connections (500ms cycle)
RED BLINK – Connection Timeout (500ms cycle)
RED – Duplicate IP Address
GREEN/RED BLINK – Network Test (500ms cycle)

10/100

GREEN – 100Mbs Connection Speed

LINK

GREEN – Link Established

Rx

GREEN – Message Being Received

PWR

GREEN – Appropriate Power Supplied to Card

Ferrites around power
and motor leads

Ferrite around looped
CAT5 Ethernet cable