Analog Output Option Card
AO-08 or AO-12
Table 4. Selecting the Monitored Output (GPD515/G5)
Terminal Parameter
Set
Value
Control
Method
(1)
Output Monitor
Scaling
1
0, 1, 2, 3
Frequency Reference
10V/100%
2
0, 1, 2, 3
Output Frequency
10V/100%
3
0, 1, 2, 3
Output Current
10V/drive rated current
5
1, 2, 3
Motor Speed
10V/100%
6
0, 1, 2, 3
Output Voltage 10V/200VAC
(400VAC)
7
0, 1, 2, 3
DC Bus Voltage 10V/400VDC
(800VDC)
8
0, 1, 2, 3
Output Power (kW)
10V/100%
9
2, 3
Torque Reference
10V/100%
15
0, 1, 2, 3
Terminal 13 Input
10V/10V
16
0, 1, 2, 3
Terminal 14 Input
10V/10V (20mA)
17
0, 1, 2, 3
Terminal 16 Input
10V/10V
18
0, 1, 2, 3
Motor Secondary Current (Iq)
10V/motor rated current
19
2, 3
Motor Exciting Current (Id)
10V/motor rated current
20
0, 1, 2, 3
Output Frequency After Soft-Start (SFS)
10V/100%
21
1, 3
ASR Input
10V/100%
22
1, 3
ASR Output
10V/motor rated current
23
1, 3
Speed Deviation / Speed Regulator Input
10V/100%
24
0, 1, 2, 3
PID Feedback
10V/100%
26
2, 3
Output Voltage Reference (Vq)
10V/230V (460V)
TD1
or
TD2
F4-01
or
F4-03
27
2, 3
Output Voltage Reference (Vd)
10V/230V (460V)
(1) Output available only when using one of the listed control methods (A1-02 setting):
0: V/Hz Mode, 1: V/Hz with Encoder (PG), 2: Open Loop Vector, 3: Closed Loop Flux Vector