Analog output option card ao-08 or ao-12, Ao-08 or ao-12 card – Yaskawa AO-08 User Manual
Page 2

Yaskawa Electric America, Inc. – www.drives.com
IG.AFD.51, Page 2 of 4
Date: 07/01/04, Rev: 04-07
Analog Output Option Card
AO-08 or AO-12
F7, G7,
GPD515/G5,
G5HHP
L1
L2
L3
T1
T2
T3
E
TD1
AO-08 or AO-12 Card
33000 PF
0V
0V
TYPICAL CIRCUIT
BOTH CHANNELS
0V
D/A
CONVERTER
200
I M
MOTOR
MCCB
SHIELD
3CN
3CN
(GREEN)
FM
AM
+
+
-
-
10K
10K
MTR
CAL
MTR
CAL
TD3
TD2
Grounding
Terminal:
F7, G7 = TB3
G5 = 12
E
Figure 2. AO-08 / AO-12 Interconnection Diagram
Table 2. Terminal Functions of the AO-08 and AO-12
Signal Level
(1)
F7/G7
GPD515/G5
Terminal
Functions
AO-08
AO-12
AO-08
AO-12
TD1
Analog signal
output channel 1
TD2
Analog signal
output channel 2
0-10VDC
0-10VDC
or
+/-10VDC
0-10VDC
0-10VDC
or
+/-10VDC
TD3 Output
Common
0V
(1) F7/G7: Selectable by setting of drive parameters F4-07 (TD1) and F4-08 (TD2).
GPD515/G5: Selectable by setting of drive parameter H4-07.
Table 3. Adjustment of Output Signal Scaling
Drive
Terminal
Gain Parameter
(1)
Setting
Range
Increment
Factory
Setting
Remarks
TD1 F4-02
0.0-
1000.0%
0.1% 100%
F7/G7
TD2 F4-04
0.0-
1000.0%
0.1% 50%
10VDC / 100 %
(2)
TD1 F4-02
0.00 to
2.50
0.01 1.00
GPD
515/G5
TD2 F4-04
0.00 to
2.50
0.01 0.50
10VDC / 1.00
(2)
(1) A gain of 0.5 will set 5VDC = 100%; a gain of 2.0 will set 10VDC = 50%.