Change

0 4/18/97

Page 6 of 6

Doc. No. 02Y00025-0422

Change 1 9/19/00

Neg Slope Time

P1-04= 0.0 Sec

P1-04 Negative Slope Time

Setting Range:

0.0 to 120.0 Sec.

Factory Default:

0.0 Sec.

Modbus Address: 0583H

Pos Slope Time

P1-05= 0.0 Sec

P1-05 Positive Slope Time

Setting Range:

0.0 to 120.0 Sec.

Factory Default:

0.0 Sec.

Modbus Address: 0584H

These parameters determine the rate at which the speed reference will change during the
“disturb” operation. P1-04 determines the decel time, and P1-05 determines the accel
time. NOTE: The selected accel/decel rates (C1-01 through C1-08) are disabled during
traverse operation. See Figure 1.




5.0 New Monitors

None.


6.0 New Alarm and Fault Codes

None.