Added Parameters:
This software does not add any new parameters to the drive.
Changed Parameters:
Refer to Appendix 1 ot the GPD 515 Technical Manual, TM 4515. The following changes result from
the installation of this software in the drive.
Parameter
Function Name
Changed
Standard
Continuous
Software
DB Software
L8-01
Internal Dynamic Braking
Max. Value
1
3
Transistor Protection
Factory Setting
0
3
L 8 - 0 1 : Internal Dynamic Braking
Factory setting: 3
Resistor Protection
Range: 0 to 3
This parameter sets both the level of protection (based on duty cycle) and whether
the dynamic braking transistor will be active when the drive is not running.
L8-01
Resistor Over-
Duty Cycle
Dynamic Braking
Setting
load Protection
(1)
Transistor Active
(2)
0
Disabled
N/A
During Run
1
Enabled
10%
During Run
2
Enabled
3%
All of the time
3
Enabled
10%
All of the time
(1)
Duty Cycle is based on 6 minute interval.
(2)
When bus voltage exceeds the DB turn on level.
Deleted Parameters:
This software does not delete any parameters from the drive.
Startup Procedure:
Use the appropriate startup procedure in Section 2 of the GPD 515 Technical Manual (TM 4515).
Doc. No. 02Y00025-0425
Page 2 of 3