beautypg.com

Table 1.21 motor ol indicator, Table 1.22 safeties open indicator, Table 1.23 drive fault indicator – Yaskawa E7B Drive Bypass System User Manual

Page 25: Table 1.24 smoke purge indicator

background image

Yaskawa Electric America, Inc.

Installation Guide IG.E7B.02 Rev: 04-11

Date: 11-1-04 Page 23 of 46

Bypass Motor OL Indicator

Safeties Open Status Indicator

Drive Fault Indicator

Smoke Purge Status Indicator

Table 1.21 Motor OL Indicator

Indicator Status

Description

On (Red)

The motor overload (S10 on schematic E7B-10) has tripped OFF de-
energizing both the Drive and Bypass Circuits.

Off

The motor overload (S10) is satisfied.

Table 1.22 Safeties Open Indicator

Indicator Status

Description

On (Red)

The NC “motor safety circuit” connected to terminals TB1-1 and TB1-9
has an open circuit condition.

Off

The NC “motor safety circuit” is satisfied or this function is disabled by
DIP switch S2-7.

Table 1.23 Drive Fault Indicator

Indicator Status

Description

On (Red)

The Drive has tripped OFF due to an internal Drive fault.

Off

The Drive is ready for operation, or operating normally.

Table 1.24 Smoke Purge Indicator

Indicator Status

Description

On (Amber)

The Smoke Purge function has been activated, the building fire control
system has closed a contact between terminals TB1-5 and TB1-9.

Off

Smoke Purge is not active, the Drive & Bypass are operating normally.