Sel–1, Read, Copy – Yaskawa Copy Unit Model for GPD 503 User Manual
Page 5: Urfy, Nodat, Proer, Caper, D ifps, Noapl, Cser

DWG. NO. 02Y00025-0415
SHEET NO. 5 OF 5
R E L . 1 0 / 2 8 / 9 6
( m - df )
Refer to Sheet 1 for latest change.
LIST OF COPY UNIT DISPLAYS
DISPLAY
DESCRIPTION
TROUBLESHOOTING
SEL–1
Memory selection display
n/a
rEAD
During read-out
n/a
CoPY
During write-in
n/a
urFY
During verification
n/a
noDAT
No constant data found at the entered
n/a
(NO DATA)
memory (memo) location.
ProEr
An attempt to read was made when READ
Turn off the switch on the Copy
(PROHIBIT
prohibit SW is turned on.
Unit to enable reading.
ERROR)
CAPEr
An attempt to copy or verify between
n/a
(CAPACITY
different Drive models was made.
ERROR)
d iFPS
Connected Drive has a different password
n/a
(DIFFERENT
from that of stored data.
PASSWORD)
EXMAPLE: Copy from GPD 503 to
GPD 333.
noAPL
READ, COPY or VRFY was attempted
Special setting for special PROM
(NOT
for special PROM Drive.
is needed.
APPLICABLE)
CSEr
An error occurred by checksum
Stored constants cannot be used.
(CHECKSUM
calculation for the stored data.
Try READ again.
E2PEr
Although an attempt to store
Use other memory No.
(E2 PROM
constants in the Copy Unit, they
E2 PROM fault in the Copy Unit.
ERROR)
cannot be stored correctly.
iFER
An error occurred in communication
Check connection between the
(I/F ERROR)
with the Drive.
Copy Unit and Drive.
CPYEr
Data could not be written in normally
Try COPY operation again.
(COPY
to the Drive in COPY operation.
ERROR)
CPF04
An attempt to write in constants to
Execute initialization of constants
(DRIVE
the Drive was made but they could not
in the Program mode.
CPF04 FAULT)
be written in normally at the Drive.
Drive constant memory element
(NVRAM, EPROM) fault. If the
same fault occurs again, replace
the Drive’s Control PCB.