Caution – Yaskawa DS386 User Manual
Page 3

Yaskawa Electric America, Inc . www.drives.com
02Y00025-0295 Page 3 OF 5
REL. 02/8/91
Table 1. Specifications of AI-14U Card
Parameter
Value
Input Signal Level
0 to 10V DC (Input Impedance: 20k
Ω
)
4 to 20mA (Input Impedance: 250
Ω
)
Input Resolution
14 bits (1/16384)
Control voltage input (from GPD 515/G5 or GPD 503): 24V (isolated)
Table 2. Terminal Functions of AI-14U
Terminal
Function
Signal Level
Notes
TC1
Analog voltage input
Input voltage: 0 to 10V
— Input Resolution: 1/16384
Input Impedance: 20k
Ω
(14 bits)
TC2
Analog current input
Input current: 4 to 20mA
— Signal Linearity: ±0.1%
Input Impedance: 250
Ω
TC3
Signal common
0V
— Terminal screws are metric size M3.
CAUTION
KEEP ANALOG SPEED REF. (I.E. CONTROL CIRCUIT) WIRING
SEPARATE FROM MAIN CIRCUIT INPUT/OUTPUT WIRING.
CAUTION
TO PREVENT ERRONEOUS OPERATION CAUSED BY NOISE
INTERFERENCE, USE SHEILDED CABLE FOR CONTROL
WIRING, AND LIMIT DISTANCE TO 10M (33 FEET) OR LESS.
IMPORTANT
Because the analog speed reference is converted by 1/16384 resolution, the
voltage source accuracy of the analog speed reference source must be con-
sidered. To ensure speed control accuracy, use a high precision power supply for
the voltage source.
Route wires from the drive and connect to the peripheral device. Refer to "Electrical Installation" in the drive’s
technical manual for further information on use of shielded cable.
5. Wiring. See Figure 3 for Analog Speed Reference connections. See Table 2 for terminal functions.
ANALOG SPEED REFERENCE
MODEL DS386