beautypg.com

Caution – Yaskawa DS386 User Manual

Page 3

background image

Yaskawa Electric America, Inc . www.drives.com

02Y00025-0295 Page 3 OF 5

REL. 02/8/91

Table 1. Specifications of AI-14U Card

Parameter

Value

Input Signal Level

0 to 10V DC (Input Impedance: 20k

)

4 to 20mA (Input Impedance: 250

)

Input Resolution

14 bits (1/16384)

Control voltage input (from GPD 515/G5 or GPD 503): 24V (isolated)

Table 2. Terminal Functions of AI-14U

Terminal

Function

Signal Level

Notes

TC1

Analog voltage input

Input voltage: 0 to 10V

— Input Resolution: 1/16384

Input Impedance: 20k

(14 bits)

TC2

Analog current input

Input current: 4 to 20mA

— Signal Linearity: ±0.1%

Input Impedance: 250

TC3

Signal common

0V

— Terminal screws are metric size M3.

CAUTION

KEEP ANALOG SPEED REF. (I.E. CONTROL CIRCUIT) WIRING
SEPARATE FROM MAIN CIRCUIT INPUT/OUTPUT WIRING.

CAUTION

TO PREVENT ERRONEOUS OPERATION CAUSED BY NOISE
INTERFERENCE, USE SHEILDED CABLE FOR CONTROL
WIRING, AND LIMIT DISTANCE TO 10M (33 FEET) OR LESS.

IMPORTANT

Because the analog speed reference is converted by 1/16384 resolution, the
voltage source accuracy of the analog speed reference source must be con-
sidered. To ensure speed control accuracy, use a high precision power supply for
the voltage source.

Route wires from the drive and connect to the peripheral device. Refer to "Electrical Installation" in the drive’s
technical manual for further information on use of shielded cable.

5. Wiring. See Figure 3 for Analog Speed Reference connections. See Table 2 for terminal functions.

ANALOG SPEED REFERENCE

MODEL DS386