beautypg.com

Analog speed reference model ds386 – Yaskawa DS386 User Manual

Page 5

background image

Yaskawa Electric America, Inc . www.drives.com

02Y00025-0295 Page 5 OF 5

REL. 02/8/91

Table 4. Adjustments of Input Signal Gain and Bias for GPD 503

GPD 503

Function

Setting

Increment

Factory Setting

Constant

Range

bn-05

Frequency command

0.0 to 1000.0%

0.1 %

10V/100.0%

gain (10V/xx%)

bn-06

Frequency command

-100 to 100%

1 %

0%

bias

B. GPD 503: See Table 4 and Figure 5.

IMPORTANT

For the Analog Speed Reference circuit to function properly, system constant Sn-04 must be set to XXX 0 and
Sn-08 must be set to XXX 0. The input to AI-14U replaces the auto speed reference signal (Terminal 13).

7. Reinstall and secure drive cover.

8. Place this instruction sheet with the drive technical manual.

THIS COMPLETES INSTALLATION OF THIS OPTION.

Figure 5. Frequency Command Gain and Bias Adjustments for GPD 503

10V

20mA

0V

4mA

SPEED
REF.
INPUT

SPEED
REF.
INPUT

FREQ.
CMD
(%)

0

FREQ.
CMD
(%)

0

GAIN

GAIN

bn-05

bn-05

bn-06
(+)

bn-06
(–)

bn-06
(+)

bn-06
(–)

BIAS

BIAS

Figure 4. Frequency Command Gain and Bias Adjustments for GPD 515/G5

10V

20mA

0V

4mA

SPEED
REF.
INPUT

SPEED
REF.
INPUT

FREQ.
CMD
(%)

0

FREQ.
CMD
(%)

0

GAIN

GAIN

H3-02

H3-02

H3-03
(+)

H3-03
(–)

H3-03
(+)

H3-03
(–)

BIAS

BIAS

ANALOG SPEED REFERENCE

MODEL DS386