Analog speed reference model ds386 – Yaskawa DS386 User Manual
Page 5

Yaskawa Electric America, Inc . www.drives.com
02Y00025-0295 Page 5 OF 5
REL. 02/8/91
Table 4. Adjustments of Input Signal Gain and Bias for GPD 503
GPD 503
Function
Setting
Increment
Factory Setting
Constant
Range
bn-05
Frequency command
0.0 to 1000.0%
0.1 %
10V/100.0%
gain (10V/xx%)
bn-06
Frequency command
-100 to 100%
1 %
0%
bias
B. GPD 503: See Table 4 and Figure 5.
IMPORTANT
For the Analog Speed Reference circuit to function properly, system constant Sn-04 must be set to XXX 0 and
Sn-08 must be set to XXX 0. The input to AI-14U replaces the auto speed reference signal (Terminal 13).
7. Reinstall and secure drive cover.
8. Place this instruction sheet with the drive technical manual.
THIS COMPLETES INSTALLATION OF THIS OPTION.
Figure 5. Frequency Command Gain and Bias Adjustments for GPD 503
10V
20mA
0V
4mA
SPEED
REF.
INPUT
SPEED
REF.
INPUT
FREQ.
CMD
(%)
0
FREQ.
CMD
(%)
0
GAIN
GAIN
bn-05
bn-05
bn-06
(+)
bn-06
(–)
bn-06
(+)
bn-06
(–)
BIAS
BIAS
Figure 4. Frequency Command Gain and Bias Adjustments for GPD 515/G5
10V
20mA
0V
4mA
SPEED
REF.
INPUT
SPEED
REF.
INPUT
FREQ.
CMD
(%)
0
FREQ.
CMD
(%)
0
GAIN
GAIN
H3-02
H3-02
H3-03
(+)
H3-03
(–)
H3-03
(+)
H3-03
(–)
BIAS
BIAS
ANALOG SPEED REFERENCE
MODEL DS386