Tag
Description
Digital_Output_1
Digital output one status (M1-M2).
Digital_Output_2
Digital output two status (M3-M4).
Digital_Output_3
Digital output three status (M5-M6).
Digital_Output_Fault
Digital output status of the fault contact (MA-MB-MC).
Digital_Output_Fault_Enable
Bit to enable to the ability to control the fault contact via the network.
Drive_State
Status code of the drive state.
Error_Code
Custom data error code provides additional information on the cause of the custom error bit.
External_Fault
Activating this bit will trigger an EF0 fault in the drive.
Faulted
Drive is in a faulted state.
FaultReset
Activating this bit will reset a fault in the drive (if resettable).
Freq_Cmd
Commanded frequency reference from the network.
Freq_Ref
Frequency reference command that is sent to the drive via the network.
MFI_3
Activating this bit will execute the function programmed for S3.
MFI_4
Activating this bit will execute the function programmed for S4.
MFI_5
Activating this bit will execute the function programmed for S5.
MFI_6
Activating this bit will execute the function programmed for S6.
MFI_7
Activating this bit will execute the function programmed for S7.
MFI_8
Activating this bit will execute the function programmed for S8.
MFO_1
Activating this bit will change the status of multi-function output 1 (M1-M2).
MFO_1_Status
Status of multi-function output 1 (M1-M2).
MFO_2
Activating this bit will change the status of multi-function output 2 (M3-M4).
MFO_2_Status
Status of multi-function output 2 (M3-M4).
MFO_3
Activating this bit will change the status of multi-function output 3 (M5-M6).
MFO_3_Status
Status of multi-function output 3 (M5-M6).
Motor_Rated_Torq
Motor rated torque as defined by the motor. Enter this value to scale the torque command. Enter “100.0”
for a range of 0-100.0%.
Motor_Speed
Motor output speed in Hz.
Net_Control
Activate the bit if start/stop control is desired through the network when b1-02
≠ 3.
Net_Ref
Activate the bit if speed reference control is desired through the network when b1-03
≠ 3.
NetCtrlStatus
Bit is active if start/stop control is through the network.
NetRefStatus
Bit is active if the speed reference is through the network.
Node_Input_Assy
Input assembly data fed into the AOI. Define this data for the AOI to operate.
Node_Output_Assy
Output assembly data fed into the AOI. Define this data for the AOI to operate.
OPE
oPE alarm is present in the drive.
Output_Current
Output current of the drive in amps.
Output_Freq
Output frequency of the drive in Hz.
PG_Count
Encoder feedback counter. The value in quadrature counts of the encoder.
Ready
Drive is in the ready state.
Reset
Fault reset to the drive is active.
RunFwd
Activate the bit to run the drive in the forward direction.
Running
Drive is in run mode.
RunningFwd
Drive is running in the forward direction.
RunningRev
Drive is running in the reverse direction.
RunRev
Activate the bit to run the drive in the reverse direction.
Torq_Ref_Limit
Torque reference or limit that is being sent to the drive. Scaled by Motor_Rated_Torq.
Torque_Actual
Torque value (U1-09) from that drive. Scaled by Motor_Rated_Torq.
UV
Drive is in an under voltage condition.
Warning
Drive is in a warning (alarm) state.
ZSP
Drive is currently at zero speed.
ZSV
Zero servo is activated in the drive.
7 AOI Data Tag Description