4.6 Connecting the Sensor to the Sunny Central
At the Sunny Central, the sensor is connected to the Sunny Central Control using the terminal strips
Z5-X5.
4.6.1 Irradiation Sensor
In this case, an analog input is used as the voltage input. To do so, the positive pole of the reference
cell is connected to terminal 5 or 7 and the negative pole of the reference cell is connected to terminal
6 or 8.
or
Duplicated wire, brown
PIN 21 (AIN-8-)
Originalader, Braun
PIN 23 (PT100-I2-)
Connection of temperature sensor PT100 to "AIN-7" in a 2-cable system
Yellow
Bridge PIN 9 (AIN-7+) with PIN 11 (PT100-I1+)
Brown
Bridge PIN 20 (AIN-7-) with PIN 22 (PT100-I1-)
Connection of temperature sensor PT100 to "AIN-8" in a 2-cable system
Yellow
Bridge PIN 10 (AIN-8+) with PIN 12 (PT100-I2+)
Brown
Bridge PIN 21 (AIN-8-) with PIN 23 (PT100-I2-)
Protect connection interfaces against weather effects.
When extending the sensor cable, protect the connection interface against weather effects
(e.g. using a junction box or terminal box).
Realizing the electrical connection
The wiring diagram provided must be used for establishing the electrical connections and
connectors.
Connection of irradiation sensor to "=Z5-X5"
Green (irradiation sensor +)
Terminal 5
White (irradiation sensor -)
Terminal 6
Connection of irradiation sensor to "=Z5-X5"
Green (irradiation sensor +)
Terminal 7
White (irradiation sensor -)
Terminal 8
Connection of temperature sensor PT100 to "AIN-8" in a 4-cable system