beautypg.com

SMA Energy Meter User Manual

Page 2

background image

EnergyMeter-IA-en-16

SMA Solar Technology AG

Procedure:

1. Connect one current transformer to each line

conductor L1, L2 and L3.

2. On each current transformer, connect one

connection cable for current measurement to

each of the secondary current terminals

(k/S1 and l/S2). Observe the permitted con-

nection cross-section of the Energy Meter (see

Section "Technical Data"):

3. Connect the connection cables for current

measurement to the Energy Meter. Observe

the prescribed torque for screw terminals (see

Section "Technical Data"):

4. Connect the connection cables for voltage

measurement to the Energy Meter. Observe

the prescribed torque for screw terminals (see

Section "Technical Data"):

5. Connect the connection cables for voltage

measurement to the corresponding line con-

ductors.

Additionally required material (not includ-

ed in the scope of delivery):
☐ 1 x network cable
Recommended cable types:
• SF/UTP, S-FTP, S/UTP, SF/FTP, S/FTP, S-STP

For further information on cable types, refer to

the Technical Information "SMA Speedwire

Fieldbus" at www.SMA-Solar.com.

Procedure:
1. Connect the network cable to the network ter-

minal (Speedwire) of the Energy Meter.

2. Connect the other end of the network cable to

a router/network switch. SMA products

which are to receive measured values must be

integrated in the same local network.

1. Cover the Energy Meter with the cover or the

contact protection of the subdistribution.

2. Switch the power supply to the subdistribution

back on.

☑ The LEDs of the Energy Meter glow during

start-up. If there is only one Energy Meter in

the system, the Energy Meter connects

automatically to SMA communication

products in the same local network. For more

information on commissioning, see the user

manual of the supported devices.

✖ The LEDs are not glowing or the

Energy Meter is not displayed by the SMA

communication products?
• Correct the error (see Section "Trouble-

shooting").

Procedure:
• Press the reset button with a sharp object and

hold it for two to six seconds.

Procedure:
• Press the reset button with a sharp object and

hold it for six seconds or longer.

Procedure:
1. Call up the Internet browser and in the ad-

dress line enter

http://energymeter“Serial number“.local

,

e.g.:
http://energymeter7435667356.local
Note: The serial number can be found on the

type label of the Energy Meter.

2. Press Enter.
☑ The user interface of the Energy Meter opens.
✖ The user interface does not open?

• Correct the error (see Section "Trouble-

shooting").

Procedure:

1. Open the user interface of the Energy Meter

(see Section "Accessing the User Interface")

2. On the homepage, select Device settings >

Current Transformer settings.

3. Activate the checkbox

Use Current Transformers.

4. Enter the required transformation ratio in the

field Current Transformer ratio.

5. Select [Apply].

.

Procedure:
1. Download the update file from

www.SMA-Solar.com and save it to your

computer.

2. Open the user interface of the Energy Meter

(see Section "Accessing the User Interface")

3. Follow the instructions in the menu

Firmware update.

Procedure:

• If more than one Energy Meter is installed in

your system and you have replaced one or

more Energy Meters, you will need to adjust

the serial number of the corresponding

Energy Meter in the Sunny Island/Sunny Boy

Smart Energy. This will avoid inaccurate me-

ter reading data in the Speedwire data mod-

ule Sunny Island/Sunny Boy Smart Energy:
– In systems without Sunny Home Manager,

enter the serial number of the

Energy Meter via Sunny Explorer in the

Sunny Island/Sunny Boy Smart Energy

(for information on changing device pa-

rameters, see user manual of the Sunny Ex-

plorer).

– In systems with Sunny Home Manager,

configure

the

Energy Meter

in

Sunny Portal (see user manual of the

Sunny Home Manager).

The status LEDs are off.
The Energy Meter is not supplied with power.
• Make sure that at least the line conductor L1

and the neutral conductor are connected to

the Energy Meter.

The status LEDs are glowing or flashing red

or orange.

An error has occurred.
• Restart the Energy Meter (see Section "Re-

starting the Energy Meter").

• Contact the SMA Service Line.

The Speedwire LEDs are not glowing.

or
The Energy Meter is not displayed by the

SMA communication product.
The network cable has not been correctly con-

nected to the network terminal.
• Make sure that the network cable is correctly

connected to the network terminal.

The Energy Meter is not integrated into the same

local network as the SMA communication prod-

uct.
• Connect the Energy Meter to the same rout-

er/network switch as the SMA communica-

tion product.

The Energy Meter provides unrealistic mea-

sured values.
The Energy Meter has been installed the wrong

way round.
• Connect and commission again.
The user interface cannot be called up via

http://energymeter“Serial number“.local.
The name resolution via Avahi (Multicast DNS) is

not working.

• Call up the user interface via the current IP ad-

dress of the Energy Meter. Call up the user in-

terface of the router and read off the IP

address of the Energy Meter (see router man-

ual).

• With Windows XP/7/8:

Install Apple Bonjour

®

(download links at

www.apple.com. Note: Apple Bonjour

®

is

also contained in Apple iTunes

®.

).

• Contact your network administrator.

Procedure:
• Dispose of the Energy Meter in accordance

with the locally applicable disposal regula-

tions for electronic waste.

The license text and corresponding information is

displayed in the user interface of the

Energy Meter. You can request the source code

with modifications from the SMA Service Line.

If you have technical problems concerning our

products, contact the SMA Service Line. We re-

quire the following information in order to pro-

vide you with the necessary assistance:
• Type and serial number of the Energy Meter

(see type label of the Energy Meter)

• Type and serial number of the SMA products

(e.g. Sunny Home Manager, Sunny Explorer,

Sunny Island)

• Error description

SMA Solar Technology AG
Niestetal

International SMA Service Line
Toll free worldwide:
00800 SMA SERVICE
(+800 762 7378423)
www.SMA-Solar.com

© 2004 to 2014 SMA Solar Technology AG.
All rights reserved.

DANGER

Danger to life due to electric shock
Lethal voltages are present in the subdistri-

bution of the household.
• Disconnect the connection point from

voltage sources and make sure it cannot

be reconnected.

• Ensure that the conductors to be con-

nected to the meter are free of voltage.

WARNING

Fire hazard
If a fuse is missing or incorrect and a fault

occurs, a fire may be caused. This can result

in death or serious injury.

• Protect the line conductors of the

Energy Meter with a fuse or a main/se-

lective circuit breaker switch, max. 63 A.

Network Terminal

IGMP protocol from version 2 must be

supported
The Energy Meter works with Multicasts. For

the correct function of the Energy Meter, all

network devices used must support the IGMP

protocol, minimum required version 2

(IGMP V2).

Commissioning

Resetting the Energy Meter to

Default Settings

Restarting the Energy Meter

Accessing the User Interface

Configuring the Current Transformer

Performing a Firmware Update

Procedure after Replacing an

Energy Meter

Troubleshooting

Disposal

Open Source Licenses