Additional Information for Installation

DC Wiring With Additional DC Distribution

When combining strings outside of the SMA DC-Disconnect, and when the combined input of a sin-
gle source circuit is greater than 15 A, use the terminal labeled COMBINED for the ungrounded
conductor. DO NOT use the terminals 1 - 4 labeled UNGROUNDED in this case.

Pay attention to all operation and safety instructions listed in the Installation Guide of the Sunny Boy.
This instruction does NOT replace the Sunny Boy Installation Guide.

For connecting the DC wires to the Sunny Boy, see Installation Guide of the Sunny Boy.

Torque Values and Wire Sizes SMA DC-Disconnect

Additional DC Source Circuit

Note: This circuit will no longer be fused so additional DC source circuit fusing may be
required in order to meet UL and NEC.

Negative Grounding

Connect the positive DC wire to the terminal la-
beled COMBINED in the SMA DC-Disconnect.

Connect the negative DC wire to the terminal la-
beled PV GROUNDED in the SMA DC-Discon-
nect.

Positive Grounding

Connect the negative DC wire to the terminal la-
beled COMBINED in the SMA DC-Disconnect.

Connect the positive DC wire to the terminal la-
beled PV GROUNDED in the SMA DC-Discon-
nect.

Terminal

in-lbs

Nm.

Wire Size

AC & DC Terminal Blocks

15

1.7

6 - 10 AWG

Combined Terminal Block

Spring Terminal

Spring Terminal

6 - 10 AWG

Grounding Electrode Conductor Block 15

1.7

6 - 10 AWG