beautypg.com

Troubleshooting – Enviro EF3 User Manual

Page 29

background image

29

Troubleshooting

6. The auger motor will not function normally.
● If the Auger gear box does not turn but the motor’s armature does try to spin then the auger is

jammed. – Try to break apart jam by poking at the jam through the drop tube. If this fails then empty

the hopper and remove the Auger Cover **Remember to re-seal the cover after installation**

● Make sure the exhaust blower is operating.
● Check the condition of the vacuum hose (located on the left side of the stove). It should not be

cracked or torn and should be installed on the top air inlet tube on the vacuum sensor.

● Check the manual reset button on the 200°F (93°C) temperature sensor. If this sensor has been

tripped, check for the cause of the over-heating before pushing the red button in. Check auger for

movement.

● If the auger still does not work, then apply 115 V AC directly to the auger motor. If the auger motor

does not work, replace it.

● By pass the 200°F (93°C) temperature sensor with a jumper wire; check the auger. If the auger

works, replace the sensor.

● Check the vacuum sensor by placing a jumper wire between the blue wire and the black wire that

are attached to the sensor. If the auger works, test to see if the exhaust blower is producing enough

vacuum.

● To test the exhaust vacuum, place a magnehelic gauge in the sensor end of the vacuum tube. It

should read 0.5” W.C. If the reading is good, replace the vacuum sensor.

● If none of the below work contact your local dealer for service.
◊ Make sure the dial-a-fire is turned on.
◊ Unplug the stove and open the side and back panels. Check all the connections to the auger motor,

auger dial-a-fire, vacuum sensor, 200°F (93°C) temperature sensor and the timing control module

against the wiring diagram in this manual.

◊ Check the voltage across the load pins of the timing module. It should be around 1 V to 2 V, cycling

to line voltage during an auger pulse. If not, replace the timing control module.

◊ If the auger motor still does not work, then attempt to by-pass the auger dial-a-fire control by

removing the leads from the timing control module’s second delay pins and placing a jumper across

the pins. If the auger now cycles very quickly, test the dial-a-fire potentiometer. If the auger did not

cycle, replace the timing control module.

◊ To test the dial-a-fire potentiometer, the potentiometer should have a range of 68KΩ to approximately

850 KΩ (± 10%). If the range is not close, replace the potentiometer.

7. The dial-a-fire has no effect on the fire (Timer Control Only).
◊ Make sure all connections to the timer control module are secure.
◊ Perform a resistance test to the dial-a-fire potentiometer by placing the two (2) test leads from a

multimeter into the leads of the potentiometer. The potentiometer should have a range of 68KΩ to

approximately 850 KΩ (± 10%).

Potentiometer Readings:

Full counter-clockwise (switched off) = open circuit, overload or infinite resistance

Low fire ...............................800 KΩ to 900 KΩ

High fire ..............................68 KΩ to 82 KΩ

If the range is not close or does not vary then replace the potentiometer.