Dial up with hardware signalling – Westermo TD-22 User Manual
Page 44
45
6177-2203
Dial up with hardware signalling
Dial-up can be made by applying an external signal to the DTR-pin in the RS-232 contact. A typical
application is an alarm signal from a PLC.
The modem reacts on the first rising edge which means that one pulse is sufficient. The signal-level
should be in compliance with the RS-232 standard. If only a relay contact is available the DSR-pin
will provide a suitable voltage.
The modem does not have a redialling function. If necessary this must be handled by other
equipment connected. We advise the DCD signal to be used as a control indicating whether
connection was made or not.
AT&B1
Dial-up using DTR.
AT&D3
Hang-up if DTR goes low.
AT&Z0=nn
The number to dial, nn, is stored in memory position 0.
Please also refer to “To use minicall”, as the minicall and the dial-up with hardware signalling can
be used together.
External signal
- TR-36B (88 pages)
- TD-36 (44 pages)
- TR-36 (36 pages)
- TR-36B (20 pages)
- IDW-90 AT (97 pages)
- GD-01 (206 pages)
- GD-01 (20 pages)
- MRI-128-F4G (175 pages)
- MRI-128-F4G (169 pages)
- GDW-11 485 (380 pages)
- GDW-11 (40 pages)
- Lynx Series (28 pages)
- ODW-720-F1 (24 pages)
- ODW-720-F2 (36 pages)
- ODW-720-F1 (20 pages)
- ODW-730-F2 (36 pages)
- ODW-730-F1 (24 pages)
- DDW-120 (24 pages)
- DDW-226-EX (24 pages)
- DDW-226-EX (24 pages)
- DR-270 (28 pages)
- DR Series (460 pages)
- ED-2x0 (20 pages)
- MRD-3x0 (199 pages)
- FD-80 (24 pages)
- FDV-206-1D-1S (24 pages)
- GD-01 US (24 pages)
- LD-01 (8 pages)
- IDW-90 (44 pages)
- Lynx-x10-F2G (16 pages)
- Lynx-x08-F2G-S2 (20 pages)
- MDI-110-F3x (16 pages)
- MR-2x0 (28 pages)
- ODW-642 (28 pages)
- PII PoE Injector (12 pages)
- Viper Series (977 pages)
- SDI-5xx (12 pages)
- RFI-xx (32 pages)
- SDI-8xx (16 pages)
- RFIR-xxx (24 pages)
- TD-29 (16 pages)
- SDW-5xx (24 pages)
- TD-23 (24 pages)
- TD-29P (16 pages)
- Viper 408 (20 pages)