12
6643-22801
I/O / Relay output
Maximum voltage/current
60 VDC / 80 mA
Contact resistance
Max 30 Ω
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
I/O / Digital input
Maximum voltage/load current
60 VDC / 2 mA
Voltage levels
Logic one: >12V
Logic zero: <1V
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
USB
Electrical specification
USB 2.0 host interface
Data rate
Up to 12 Mbit/s (full-speed mode)
Circuit type
SELV
Maximum supply current
500 mA
Connection
USB receptacle connector type A
Console
Electrical specification
LVTTL/LVCMOS-level
Data rate
115.2 kbit/s
Data format
8 data bits, no parity, 1 stop bit, no flow control
Circuit type
SELV
Connection
2.5 mm jack, use only Westermo cable 1211-2027
RJ-45 connector (Front view)
Male
Female
Pin 8
Pin 1
Pin 1
Pin 8
Pin 8
Pin 1