Troubleshooting, Table 4: scan led blink codes – WattMaster VAVBOX User Manual

Page 21

background image

VAVBOX Controller

Technical Guide

21

Using LED’s To Verify Operation

The VAVBOX controller is equipped with LEDs that can be used as
very powerful troubleshooting tools. The VAVBOX controller board
has three LEDs. Two of these LEDs are used in troubleshooting. See
Figure 12 for the LED locations. The LEDs and their uses are as fol-
lows:

“REC”
This LED will light up to indicate system communications.

“PWR”
This LED will light up to indicate that 24 VAC power has been applied
to the controller.

“SCAN”
This is the diagnostic blink code LED. It will light up and blink out
diagnostic codes.

CX6

SW1

U10

75176

EXPANSION

Q3

Q2

D3

VR1

7824

R17

R16

U7

C7

R15

POWER

R21

D4

R26

LD3

L1

SCAN

REC

R12

C6

R11

TOKEN

NET

LD2

32

R14

R13

R100

LD1

C5

D1
K1

V2

K2

D2

ACTUATO

R

R10

R9

PJ2

V1

C4

CX10

8

16

2

4

ADDRESS

ADD

1

U6

PJ1

C3

R8

“SCAN”
Diagnostics LED

“REC” LED

“PWR” LED

Figure 11: LED Locations

“REC” LED Operations
When the controller is communicating this LED will flicker. If it does
not flicker check the MiniLink and/or CommLink that is connected to
the Power/Comm board which connects to your VAVBOX controller
and make sure the MiniLink and/or CommLink is powered up and prop-
erly connected to the Power/Comm board.

“PWR” LED Operations
When the WMVAV Controller is powered up the “PWR” LED should
light up and stay on continuously. If it does not light up, check to be
sure that the modular connector is connected to the board, that the con-

nections are tight and the tab is locked on the connector. Be sure power
is connected and turned on to the Power/Comm board and that the modu-
lar cable connector is securely connected. If after making all these checks
the “PWR” LED does not light up, the board is probably defective.

“SCAN” LED Operations
As previously described when the board is first powered up the LED
will do the following:

Flashes Once

Off for 5 seconds

SCAN LED blinks the board address
(Address 14 = 14 blinks)

5 second pause

20 second time delay - LED blinks 20 times

LED blinks slowly as damper moves towards the open
position. The LED blinks fast as the damper moves
towards the closed position.

After the above steps the status code is repeatedly blinked every 10
seconds to indicate controller status. The status blink codes are listed in
the following table in order of priority.

:

LED Blinks This

Number Of Times

Blink Code

Description

1

Normal Operation. No Alarm

Conditions Exist

2 Push-button

Override

Or

Group Override Is Active

3 Communication

Failure

4 Bad

Airflow

Sensor

5 Bad

or

Missing

Space Sensor

6 Damper

Failure

7

Damper Feedback Failure

Table 4: SCAN LED Blink Codes

Only the highest priority failure code will be shown. You must correct
the highest priority alarm before other problems will be indicated.

If the “SCAN” LED does not operate as indicated above, first check
the address switch setting. See Figure 10 for correct address switch
setting procedures. If the address switch setting is correct and the
“SCAN” LED still does not behave as indicated above contact Watt-
Master Controls Technical support.

Note: Power to the controller being addressed must always

be cycled after changing address switch settings in or-
der for the changes to take effect.

Troubleshooting