Wcc iii alarming, Analog alarm limit, Alarm call-out – WattMaster WCC III part 11 User Manual

Page 3: Analog input screen

background image

11. WCC III ALARMING

WCC III Technical Guide

11-1

SECTION 11:

WCC III ALARMING

__________________________________________

Alarm Call-Out

The WCC III - MCD will automatically E-mail an alarm or alarms
to an E-mail address or to multiple E-mail addresses. There are
eight different alarm types or alarm classes - each with their own
priorities. Only the fi rst fi ve alarm types or classes can “E-mail
out”; each of these fi ve alarm types can E-mail up to 12 separate
E-mail addresses. You could also send an E-mail to Text message
your cell phone, depending on your service plan with your cellular
phone provider.

Analog Alarm Limit

Each analog input on a satellite can have a low and high limit
assigned to it on the Analog Input Screen. If the value of the analog
input falls below the low limit or rises above the high limit, the
system automatically generates an alarm.

For example, assume that the analog input in question is a
room temperature sensor located in an offi ce space. If the space
temperature falls below 68 °F or rises above 80 °F during the
occupied period, we want an alarm to be generated. To set up the
alarm limits, fi rst sign on by accessing the System Parameters
Screen
and entering your password. An access level of 1 or greater
is required to enter or change alarm limits. An access level of 2 or
greater is required to enter or change what the alarm is controlled
by, the alarm type, and the alarm messages. After you are signed
on, return to the Main Menu, place the cursor over “ANALOG
INPUT” and press

. Then place the cursor over one of the

eight analog inputs and press

. An Analog Input Screen

similar to what is shown in Figure 11-1 should come into view:

Figure 11-1: Analog Input Screen

Alarm Call-Out

Satellite # 1

ANALOG INPUT # 1

Description: RM101

Type: Analog General

Pattern for values associated with this input: xxx.x

Units @ 0% scale: 0.0 DEG.

Units of Measure message #: 1

@ full scale: 100.0 DEG.

Filter time constant: 8 seconds

ALARMS

Controlled

by:

W1

Limits

Low

High

Alarm Type: 1

On

65.0 80.0 DEG.

Alarm Message #’s:

Low 2 High 1

Off

50.0 100.0 DEG.

Alternate limits selected by: ....

On (alt)

0.0

0.0 DEG.

Off

(alt)

0.0

0.0

DEG.

Limit overlap time

after control change: 20 minutes

Local set

55.0 90.0 DEG.

BINARY SETPOINT

OFF Above

0.0 DEG.

On Message #: 0

OFF Below

0.0 DEG.

Off Message #: 0

HOME for menu

ANALOG INPUT SCREEN