WCC III
Technical Specifi cations
WCC III added system improvements over the WCC II
system:
•
Increased the Global Analogs from 128 to 256
•
Increased the Global Binaries from 256 to 512
•
Increased the Week Schedules from 32 to 128
•
16 dedicated PID programs
•
Since the system is now internet based,
multiple workstations are now supported.
SAT III controller added improvements over the SAT II
controller:
•
Relay outputs instead of “Chipswitches”
•
LED status indicators for the relay outputs
•
HSS expansion port – supports new Binary
Input, Binary Output boards.
•
Added HSS Binary Outputs to SAT III (Up to
16 more relay outputs)
•
The SAT III has a 12 bit A to D converter,
while the SAT II has a 10 Bit A to D converter.
•
Analog Inputs of 0 to 1 VDC, 0 to 5 VDC, 0 to
10 VDC, 4 to 20mA, and Thermistor sensors
are now supported.
Recommended Computer for the WCC III program:
•
Pentium 4 computer or better that is running
at 2 GHz or faster
•
1 Gig RAM minimum
•
Windows XP-Pro
•
80 Gig Hard Drive or larger
•
High Speed internet access (cable modem
preferred)
•
Printer (optional for data print outs)
Computer Power Requirements (WCC III-MCD):
•
96 to 143 VAC 50/60 Hz 200 Watts
•
Use dedicated 120 VAC circuit (4-3 wire
ground plug required)
•
(UPS is recommended)
SAT III Power Requirements:
•
24 VAC @ 1 Amp
Communications Loop:
•
Each communications loop communicates
with up to 60 SATs. (4 loops are possible)
•
Communications wire is 18 gage twisted with
shield.
•
4000 feet to furthest Satellite.
•
Fiber Optics
Internet Access Requirements:
•
High Speed Access (cable modem is
preferred)
Operating Temperature:
•
50 to 100 degrees Fahrenheit, 10% to
90% (non condensing)