WCC III Provides

Comfort And Monitoring Features

Improved Comfort

Happy People: Comfortable tenants do not move out,
and comfortable employees work more effi ciently. The
WCC III is designed to monitor and control each terminal
unit in the building. Control is precise, and alarms are dis-
played when any temperature exceeds limits. Corrective
action can be taken before occupants become aware of
a problem.

Tenant Override and Report:

The override allows up to 500 different tenants to override
lights, heat, and air conditioning (or other functions) for a
selectable time period. Overrides are logged and totaled
by tenant and subcode for monthly billing purposes. Up to
12 month log is stored by month for each tenant.

Remote Monitoring/Alarm E-mail

Increases Effi ciency For Owners

Of Multiple Buildings

The WCC III system is supplied with remote access for
authorized operators. Setpoints, schedules, etc., may be

changed and system status monitored from this remote
location. Thus, the performance of multiple buildings can
be monitored from a single location and alarm reports au-
tomatically received at this or any other location through
the alarm e-mail function of the WCC III.

Enhanced Graphic Option

An enhanced graphics program (WGCC3) with standard
symbols and drawing package is available for the user de-
siring further refi nement of graphic capability. This is an
optional upgrade.

Internet Access:

Improves communication on large facilities: The ability
to have multiple operators that can have access to the
system simultaneously. This truly optimizes system per-
formance by coordinating all service maintenance and
operators’ input in one operating program.

OE210
TYPICAL
SENSOR

(X8)

ON/OFF RELAY
PUMPS, LIGHTS,
ETC.

OE320

TUC-2R

OE331

TUC-5R+

OE213
TYPICAL
SENSOR

OE421- SAT III
CONTROLLER

OE454/OE455/OE456

SAT 3C/D/F

CONTROLLER

OE213
TYPICAL
SENSOR

WCC II TO WCC III
GLOBAL BRIDGE

WCC III-MCD

SINGLE PULSE
INPUT FROM
POWER METER

UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.

VAV BOX

16 OUTPUTS

PER SAT III

TO THE ISP
(INTERNET SERVICE PROVIDER)
CONNECTION TO THE INTERNET
(BY OTHERS)

HIGH SPEED CABLE
MODEM / DSL ROUTER

ETHERNET
CABLE

Optional B-OUT Board

( 8 RELAY OUTS)

(2 PER SAT III)

Optional B-INPUT Board

( 8 BINARY INPUTS)

(2 PER SAT III)

HSS PORT

HEAT PUMP

GND

24VAC

C

R/T

SHLD

COMM T

COMM R

DRIVER

485

EEPROM

VBAT

COMM

CHASSIS GND

POWER

SAT II STAT

SAT II

SAT III

PROGRAM SOCKET

YS102210 REV 1

GLOBAL BRIDGE

MADE IN USA

ADDRESS

24C128

PCF8583

LT1785

WATTMASTER CONTROLS INC

CONNECTION
TO OLD WCC II
MANCHESTER
COMM LOOP

PULSE 1
PULSE 2
PULSE 3
PULSE 4
PULSE 5
PULSE 6
PULSE 7
PULSE 8
STAT REC
STAT XMIT
LOCAL SET
STATUS

COMM

ADD

1

2

4

8

16

32

64

128

ADDRESS

SATIII-P

PULSE METER BOARD

ATTMASTER CONTROLS

YS102268 REV0

MADE IN USA

P1

P2

P3

P4

P5

P6

P7

P8

GND

GND

POWER

SEL

TEST

LOCAL

L DIS

OPT 1

OPT 2

OPT 3

SH

R

T

24 VAC

GND

OPTIONS

PULSE INPUTS

HSS PORT

MULTIPLE PULSE
INPUTS FROM
POWER METERS

OE455-P

SAT 3P

CONTROLLER

UP TO 60 TOTAL SAT III
OR SAT 3C/D/F/P PER LOOP.
THERE ARE 4 POSSIBLE

SAT III RS485
COMMUNICATIONS LOOPS
(UP TO 239 SAT III MAXIMUM)

P 102224

L

POWER AND
SWITCHABLE COMM

USUALLY ONE
OR TWO PER
FLOOR

FIBER OPTIC LINES
MAXIUM OF 2.5 MILES
(USES "ST" CONNECTORS)

BUILDING # 2

OE421- SAT III
CONTROLLER

OE421- SAT III
CONTROLLER

OE320

TUC-2R

OE213
TYPICAL
SPACE
SENSOR

OE455

SAT 3D

CONTROLLER

VAV BOX

PL102335
RS-485 TO FIBER
OPTIC ADAPTOR

USED IN MULTIPLES
OF TWO

PL102335
RS-485 TO FIBER
OPTIC ADAPTOR

SAT COMM LOOP

SAT COMM LOOP

SAT COMM LOOP

UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.

TUC COMM LOOP

“P” MODE ADDRESSING NOTES

SAT III ADDRESSING STARTSAT

ADDRESS NUMBER 8.

EACH "P" MODE SAT III TAKES UP

(8) SAT III LOGICAL ADDRESSES.

THERE ARE ONLY (8) USED ACTIVE

INPUTS PER SAT 3P.

ANALOG INPUT #1 (PULSE INPUT #1)

ON EACH SAT III ADDRESS IS ACTIVE.

ALL OTHER INPUTS AND OUTPUTS ON

THE SAT 3P ARE NOT FUNCTIONAL.

TOTAL WIRING FOR EACH INPUT NOT

TO EXCEED 100 FEET.

USE 18 GAUGE TWISTED PAIR WITH

SHIELD FOR EACH PULSE METER

CONNECTION.

CONNECT THE SHIELD WIRE TO GND.

WCC III Typical

System Schematic